A17.1-1996 : Elevators
|
2.36 - Hydraulic Cylinders
|
302.3
|
No
|
No
|
1) Where valves and cylinders use packing glands or seals, they shall be examined and maintained to prevent excessive loss of fluid. Packing needs replacing, mechanic had to empty a full 5 gallons of oil from collection bucket. Ref: 1206.5b
|
4/25/2019
|
|
A17.1-1996 : Elevators
|
5.11 Plunger and Cylinder
|
1206.5b(4)
|
No
|
No
|
1) Where valves and cylinders use packing glands or seals, they shall be examined and maintained to prevent excessive loss of fluid. Packing needs replacing, mechanic had to empty a full 5 gallons of oil from collection bucket.
|
6/23/2020
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(a)(1)
|
No
|
No
|
1) A record that shall include the maintenance tasks listed with the associated requirements of Section 8.6 identified in the Maintenance Control Program. Ref: 8.6.1.4.1(a)(1)
|
2/11/2021
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.2 Callbacks (Trouble Calls) Documentation
|
No
|
No
|
2) A record of callbacks shall be maintained and shall include the description of reported trouble, dates, time, and corrective action(s) taken that are reported by any means to elevator personnel. Ref: 8.6.1.4.2
|
2/11/2021
|
|
A17.1-2016 : Elevators
|
5.15 - Overspeed Valve
|
8.6.5.16.5
|
No
|
No
|
3) Overspeed valves, where provided, shall be inspected and tested to verify that they will stop the car, traveling down with rated load. Due for 5-year testing. Ref: 8.6.5.16.5 Note: This Shall Be Done Next Year, during the annual inspection.
|
2/11/2021
|
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
1001.2(a)(17)
|
Yes
|
No
|
Auxiliary lowering unit inoperable
|
11/23/2022
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
Yes
|
No
|
Battery lowering is not working properly. Re-inspection required
|
12/1/2022
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
Yes
|
No
|
The battery back-up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors, needs repaired. Re-inspection required
|
12/10/2024
|
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
211.2
|
Yes
|
No
|
Emergency return unit is inoperable and shall be repaired, or replaced. Reinspection required.
|
12/9/2025
|