Inspection
Inspection Details
Equipment ID
8106
8106
Inspection Date
11/9/2024
11/9/2024
Inspection Type
Reinspection
Reinspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Timothy Roberts
Timothy Roberts
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
d3316b7a-f3f6-454d-aa38-def2561f9698
d3316b7a-f3f6-454d-aa38-def2561f9698
Location
GM Truck Assembly Plant
1500 Hwy A, Wentzville, MO
Phone: (314) 226-8291
Email: demetrius.bell@gm.com
1500 Hwy A, Wentzville, MO
Phone: (314) 226-8291
Email: demetrius.bell@gm.com
Owner
Attn: Harold Bean
General Motors Company
1500 Hwy A, Wentzville, MO 63385
Phone: (636) 327-2731
Alt Phone: (363) 368-1526
Email: harold.1.bean@gm.com
General Motors Company
1500 Hwy A, Wentzville, MO 63385
Phone: (636) 327-2731
Alt Phone: (363) 368-1526
Email: harold.1.bean@gm.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | Repair machine room lighting. | 8/20/2019 | ||
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)(12) - | Phase II sign missing in car. | 8/20/2019 | ||
MO Minimum : Elevators | (A) - Hoistways | (A)16 | Cover all uncovered electrical boxes. | 9/4/2020 | ||
A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | Repair lower panel section of bi-parting doors at both lower landings, care side. Door skin separating from trucking sill. | 9/4/2020 | ||
A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | x | Repair or replace cab emergency lighting. | 9/21/2020 | |
A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | Repair machine room lighting. | 9/4/2020 | ||
A17.1-1996 : Elevators | 2.33 - Tanks | 1206.5b | Remove scavenger pump from pit. The amount of oil leakage cannot be monitored. | 1/18/2022 | ||
A17.1-1996 : Elevators | 2.33 - Tanks | 1206.5b | Remove scavenger pump from pit. The amount of oil leakage cannot be monitored. | |||
MO Minimum : Elevators | (I) - Pits | (I)1 | The elevator pit floor is flooded with water, pit should be kept clean & dry. | |||
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Test incomplete because elevator broke down, only thing that was completed was fire service. Re-inspection required | 6/9/2023 | |
A17.1-2016 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5.1 Examination and Maintenance | x | x | Packing is bad. Piston is worn past holding the packing, replace jack | 10/25/2024 |
A17.1-2016 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. | 11/9/2024 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.10 Acceptance Inspection and Test | x | All phases of fire service and all initiating devices shall be tested. | 11/9/2024 | |
A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | Emergency power operation shall be tested. | 11/9/2024 |