Inspection
Inspection Details
Equipment ID
13447
13447
Inspection Date
11/26/2018
11/26/2018
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
David Tiemann
David Tiemann
Relief Valve Pressure
Slide
5
5
Governor Rope Pull
50/140
50/140
Door Closing Force
22/17
22/17
External ID
f65c61bc-49c2-46d8-92e5-e8cb117e54c2
f65c61bc-49c2-46d8-92e5-e8cb117e54c2
Location
St Louis Properties #1
3733 LINDELL BLVD, SAINT LOUIS, MO
3733 LINDELL BLVD, SAINT LOUIS, MO
Owner
St Louis Properties
3701 LINDELL BLVD, SAINT LOUIS, MO 63108-3425
3701 LINDELL BLVD, SAINT LOUIS, MO 63108-3425
Billing
Attn: St Louis Properties
3701 LINDELL BLVD, SAINT LOUIS, MO 63108-3425
3701 LINDELL BLVD, SAINT LOUIS, MO 63108-3425
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-1996 : Elevators | 3.23 - Suspension rope | 212 | x | Suspension ropes have rouge and are undersized. Re-inspection required | 10/16/2024 | |
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | Pit needs to be cleaned | |||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not work. Re-inspection required | 10/16/2024 | |
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | Pit light does not work | |||
A17.1-1996 : Elevators | 3.20 - Governor rope | 1001.2(c)(26) | x | Governor rope has grease all over it, should not be greased. Clean grease off rope. Re-inspection required | 10/16/2024 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | x | Ropes have been replaced but got twisted during testing. Take corrective action and re-test. Unit left shut down by maintenance company. | 10/16/2024 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Testing incomplete. Items to be completed: door closing force, SOS, 100% Safety Set, Slide, 125% weight, Emergency light/bell/phone, runby. | 2/18/2025 | |
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | Fire service testing must be documented monthly. | |||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |||
A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | Machine room door shall be self-closing and self-locking and operable from the interior space without the use of a key. Door cannot be opened inside machine room. | |||
A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | Machine room lighting needs to be repaired. One or more bulbs are not working. | |||
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Testing incomplete. Items to still be tested: SOS, 100% safety set, 125% weight, emergency light/bell/phone, runby. |