Inspection
Inspection Details
Equipment ID
14723
14723
Inspection Date
11/16/2018
11/16/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jeffrey Krug
Jeffrey Krug
Mechanic Name
Kurt Warttig
Kurt Warttig
Relief Valve Pressure
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
n/a
n/a
External ID
d2deff8a-5a4d-43b7-a843-bdd5511f1ae6
d2deff8a-5a4d-43b7-a843-bdd5511f1ae6
Location
Union Ave Christian Church
733 UNION BLVD, SAINT LOUIS, MO
733 UNION BLVD, SAINT LOUIS, MO
Owner
Union Ave Christian Church
733 UNION BLVD, SAINT LOUIS, MO 63108-1037
733 UNION BLVD, SAINT LOUIS, MO 63108-1037
Billing
Attn: Union Ave Christian Church
733 UNION BLVD, SAINT LOUIS, MO 63108-1037
733 UNION BLVD, SAINT LOUIS, MO 63108-1037
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 1/9/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 1/9/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 1/9/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | The 1st floor hall and car call buttons shall be operational. | 1/9/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | All means of access to elevator machine rooms shall be of a permanent nature and shall be constructed and maintained in a clear and unobstructed manner. Access to the roof shall not be fold out ladder. | 1/9/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | MCP required on site | 11/10/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Ensure that ladder to access roof/machine room is safe. | 11/10/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | Yes | Ropes slip traction during 125% weight testing. Unit has been red-tagged. | 11/3/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The pit light shall work. | 11/10/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. Remove excess debris. | 11/10/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/10/2023 |