Inspection
Inspection Details
Equipment ID
8651
8651
Inspection Date
11/28/2018
11/28/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Timothy Cook
Timothy Cook
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
NA
NA
Door Closing Force
19
19
External ID
d463f30b-3020-429a-a884-e3aa99f7b944
d463f30b-3020-429a-a884-e3aa99f7b944
Location
Clayton Corporate Park Management Company
600 CORPORATE PARK DR, CLAYTON, MO
600 CORPORATE PARK DR, CLAYTON, MO
Owner
Clayton Corp Park Management Company
700 CORPORATE PARK DR, CLAYTON, MO 63105-4209
700 CORPORATE PARK DR, CLAYTON, MO 63105-4209
Billing
Attn: Clayton Corporate Park Management Co.
600 CORPORATE PARK DR, CLAYTON, MO 63105-4204
600 CORPORATE PARK DR, CLAYTON, MO 63105-4204
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Written maintenance control program shall be kept on site for each elevator. | 12/18/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair phone in car | 9/23/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.5 Code Data Plate | No | No | There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to (A17.1 1993), as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. | 10/1/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Two-way communication could not be established. Repair/replace this phone for proper operation and passenger safety. Reinspection required. | 9/10/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | A17.1 2016-8.6.4.19.6 The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: - The proximity door protection device is not rendered inoperative when phase I operation is initiated. | 9/10/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. | 9/10/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | The smoke detector at the top of the hoistway has become detached and shell be secured to the electrical junction box. | 10/1/2025 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Governor rope is rouged and undersized. Need to replace governor rope. Re-inspection required | 10/1/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.5 Code Data Plate | No | No | There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to (A17.1 1993), as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. | 10/1/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | The elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Re-inspection required | 10/1/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | The smoke detector at the top of the hoistway has become detached and shall be re-secured to the electrical junction box. | 10/9/2025 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | Yes | The governor rope is rouged and undersized. Red-tagged, Re-inspection required | |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | The smoke detector at the top of the hoistway has become detached and shall be re-secured to the electrical junction box. |