Inspection
Inspection Details
Equipment ID
2675
2675
Inspection Date
12/16/2024
12/16/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Wright
Michael Wright
Mechanic Name
Anthony Henthorne
Anthony Henthorne
Relief Valve Pressure
N/A
N/A
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
22
22
External ID
6beec569-0cb3-412c-b77a-e848986b5a41
6beec569-0cb3-412c-b77a-e848986b5a41
Location
Administrative Center
5115 Oak St, Kansas City, MO
Phone: (816) 235-1363
Email: cfmaccounting@umkc.edu
5115 Oak St, Kansas City, MO
Phone: (816) 235-1363
Email: cfmaccounting@umkc.edu
Owner
Attn: Robert Wren
UMKC- Campus Facilities Mgmt
1011 E 51st St, Kansas City, MO 64110
Phone: (816) 235-1363
Email: rwren@umkc.edu
UMKC- Campus Facilities Mgmt
1011 E 51st St, Kansas City, MO 64110
Phone: (816) 235-1363
Email: rwren@umkc.edu
Billing
Attn: Marc Bates
UMKC- Campus Facilities Mgmt
1011 E 51st St, Kansas City, MO 64110
Phone: (816) 235-1363
Email: batesmw@umkc.edu
UMKC- Campus Facilities Mgmt
1011 E 51st St, Kansas City, MO 64110
Phone: (816) 235-1363
Email: batesmw@umkc.edu
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service test and post test log in the machine room | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | the certificate in the machine room is to be updated every year with the new copy | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | the wire from the relay on the upper right of the controller to the terminal block on the lower left needs to be ran behind the controller panel not in front of the open relays | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | the machine room fire extinguisher does not have a current inspection tag | |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | No | No | the infrared edge is to be disabled during fire service phase 1 and 2, it currently works during both phase 1 and 2 | 10/11/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | No | No | the fire service audible signal did not work | 10/11/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | replace the emergency light battery it is dead | 10/11/2021 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | infrared door edge is to be disabled on fire service operation phase 1 and 2 | 11/16/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | Yes | No | the audible signal for fire service phase 1 recall did not work | 11/16/2022 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | on fire service phase 2 operation the doors open all the way even after the door open button is released | 11/16/2022 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | the stop switch is to be disabled on fire service phase 1 recall | 11/16/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | the emergency lights did not come on | 11/16/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | the state operating certificate in the machine room needs to be updated with the current operating certificate annually | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | emergency lights did not come on, replace the emergency light battery | 11/3/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | No | No | the fire service phase 1 recall audible signal did not work | |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | door reopening devices that are sensitive to smoke or flame shall be rendered inoperative on fire service | 11/3/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Replace emergency light battery,it is dead | 12/16/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate in the machine room expired in 2017, update with current state operating certificate when received | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine room fire extinguisher inspection tag is expired, have the fire extinguisher inspected and tagged | |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Door reversal device that can be effected by smoke shall be disabled on fire service phase 1 recall | 12/16/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | No | No | The audible signal did not work on fire service recall | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace all pit equipment that is rusted and falling apart weakened metal structures no longer meet factor of safety minimums, see ladder and pit channels | |
| MO Minimum : Elevators | (I) - Pits | (I)2 | No | No | replace pit channel that is rusted and galling apart, weakened metal pit channel no longer meets factor of safety minimums | |
| MO Minimum : Elevators | (I) - Pits | (I)5 | No | No | the bottom of the pit ladder is rusted and is falling apart, the only thing supporting weight on the ladder is the wall mounts | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | Yes | Emergency lights inoperative. |