Inspection
Inspection Details
Equipment ID
13662
13662
Inspection Date
12/5/2024
12/5/2024
Inspection Type
Reinspection
Reinspection
Inspector Name
Kevin Hecht
Kevin Hecht
Mechanic Name
Christian Schickedanz
Christian Schickedanz
Relief Valve Pressure
NA
NA
Slide
13"
13"
Governor Rope Pull
75/500
75/500
Door Closing Force
23
23
External ID
118d1716-6568-4638-a3fe-72c118fb3ea7
118d1716-6568-4638-a3fe-72c118fb3ea7
Location
Kiener East Garage
500 Pine St, St. Louis, MO
Phone: (314) 241-4262
Email: bill.vansambeek@intpark.com
500 Pine St, St. Louis, MO
Phone: (314) 241-4262
Email: bill.vansambeek@intpark.com
Owner
Attn: Inter Park Holdings LLC
Inter Park Holdings LLC
100 S 9th St, St. Louis, MO 63102
Phone: (000) 000-0000
Email: bill.vansambeek@intpark.com
Inter Park Holdings LLC
100 S 9th St, St. Louis, MO 63102
Phone: (000) 000-0000
Email: bill.vansambeek@intpark.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Need phase 2 fire signage in car. | 1/15/2021 |
| conversion | conversion | conversion - reinspect | Yes | No | Emergency light and bell shall work. | 10/1/2018 |
| conversion | conversion | n/a | No | No | Position indicator in car shall work | 1/15/2021 |
| conversion | conversion | conversion - reinspect | Yes | No | Return to phase 1 fire service did not work when turning phase 2 switch to off. | 10/1/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Door close operation shall require constant pressure on phase 2 fire service. | 10/1/2018 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | A category 5 inspection is required. | 10/3/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Phase 1 and Phase 2 key switches shall be keyed the same. | 10/3/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Provide Phase 2 instructions in the car. | 10/3/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell shall work. | 10/3/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Emergency lights shall work. | 1/15/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/15/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | No | No | The lighting in the stairwell that leads to the machine room shall be operational. | 12/8/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. | 11/21/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/21/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | Yes | Car failed unintended motion test with 125% load, did not stop within allowed distance. Elevator Red Tagged. | 10/22/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | Yes | Mainline disconnect broke during testing and needs repair. Elevator Red Tagged. | 10/22/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The remainder of the annual and category 5 test needs to be completed. Note: Hoistway, hall door interlocks, car gate switch and restrictor, emergency light, alarm, 2 way-communication, and fire service have been inspected. | 10/22/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | Yes | Unit is still under red tag condition. Unintended motion with 125% load and counterweight buffer testing must be performed to complete category 5 testing and remove red tag. | 12/5/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. |