Inspection
Inspection Details
Equipment ID
8655
8655
Inspection Date
11/30/2018
11/30/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Timothy Cook
Timothy Cook
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
18
18
External ID
e831e3ca-01a5-435c-b4f1-e550f35120e3
e831e3ca-01a5-435c-b4f1-e550f35120e3
Location
Clayton Corporate Park Management Company
700 CORPORATE PARK DR, CLAYTON, MO
700 CORPORATE PARK DR, CLAYTON, MO
Owner
Clayton Corp Park Management Company
700 CORPORATE PARK DR, CLAYTON, MO 63105-4209
700 CORPORATE PARK DR, CLAYTON, MO 63105-4209
Billing
Attn: Clayton Corporate Park Management Co.
600 CORPORATE PARK DR, CLAYTON, MO 63105-4204
600 CORPORATE PARK DR, CLAYTON, MO 63105-4204
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Written maintenance control program shall be kept on site for each elevator. | 12/18/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.5 Code Data Plate | No | No | There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to (A17.1 1984), as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. | 11/18/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | There is no signage for Firefighters Operation by the phase I and phase II key switches. Obtain the correct signage from the building code addition that this elevator was designed to meet. | 11/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.5 Code Data Plate | No | No | There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to (A!&.1 1984), as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. | 11/18/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | There is no signage for Firefighters Operation by the phase I and phase I key switches. Obtain the correct signage from the building code addition that this elevator was designed to meet. | 11/18/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.10 Acceptance Inspection and Test | Yes | No | All call stations in lobby must be permanently mounted. | 11/18/2025 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | Yes | No | Machine room lighting needs to be checked. | 11/18/2025 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 | Yes | No | Pit lighting needs to be checked. | 11/18/2025 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Seal all penetrations in hoistway. | 11/18/2025 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.1.1 | Yes | No | Reinstall handrail on steps going into machine room. | 11/18/2025 |