Inspection
Inspection Details
Equipment ID
10535
10535
Inspection Date
12/12/2024
12/12/2024
Inspection Type
Other Inspection
Other Inspection
Inspector Name
Kevin Hecht
Kevin Hecht
Mechanic Name
Joshua Clampitt
Joshua Clampitt
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
3b3ca972-18f0-499f-a77b-09c21dbeb641
3b3ca972-18f0-499f-a77b-09c21dbeb641
Location
West Pine Apts
4490 W Pine Blvd, St. Louis, MO
Phone: (314) 531-4770
Alt Phone: (314) 286-4221
Fax: (314) 286-4382
4490 W Pine Blvd, St. Louis, MO
Phone: (314) 531-4770
Alt Phone: (314) 286-4221
Fax: (314) 286-4382
Owner
Attn: Matthew DeRienzo
The Habitat Company
4490 W Pine Blvd, St. Louis, MO 63108
Phone: (314) 531-4770
Email: pwerner@slha.org
The Habitat Company
4490 W Pine Blvd, St. Louis, MO 63108
Phone: (314) 531-4770
Email: pwerner@slha.org
Billing
Attn: Sabrina Hill
The Habitat Company
4451 Forest Park Ave, St. Louis, MO 63108
Phone: (618) 978-3338
Email: pwerner@slha.org
The Habitat Company
4451 Forest Park Ave, St. Louis, MO 63108
Phone: (618) 978-3338
Email: pwerner@slha.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Phone not working. | 6/21/2018 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | The cab ceiling is of the open egg-crate type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers. | 12/11/2019 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 1001.2(b)(1) | No | No | The elevator machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. The door currently does not lock securely. | 12/11/2019 |
| A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | No | No | Fire sprinklers are present in the elevator hoistway and pit. A shunt trip disconnects shall be added and electrically tied into the heat detectors to remove power from the elevator before the application of water. Reinspection and testing will be required. | 12/11/2019 |
| A17.1-1996 : Elevators | 2.14 - Code data plate | 215 | No | No | There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to, as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. Upon investigation, it has been determined that the last major alteration occurred on 11/23/1999. The proper code edition that this elevator was installed to is A17.1 1996. | 12/11/2019 |
| A17.1-1996 : Elevators | 2.19 - Gears, bearings, and flexible couplings | 1001.2(b)(17) - no reinspect | No | No | A grease seal on the drive machine is leaking excessively and shall be replaced. | 12/11/2019 |
| A17.1-1996 : Elevators | 3.10 - Hoistway construction | 1001.2(c)(16) | No | No | A temporary construction barrier was installed in the elevator hoistway between the elevator cars. This barrier is designed for only temporary use and shall be removed from the hoistway. | 12/11/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Check and repair the programming of this phone for proper operation and passenger safety. Reinspection required. | 6/1/2020 |
| A17.1-1996 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 210.4 | No | No | Fire sprinklers are present in the elevator hoistway and pit. A shunt trip disconnects shall be added and electrically tied into the heat detectors to remove power from the elevator before the application of water. Reinspection and testing will be required | 5/18/2020 |
| A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | No | No | Fire sprinklers are present in the elevator hoistway and pit. A shunt trip disconnect shall be added and electrically tied into the heat detectors to remove power from the elevator before the application of water. REINSPECTION REQUIRED. | 9/1/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Car top needs to be cleaned | 8/19/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Car door restrictor is not working. Re-inspection required | 5/16/2023 |
| A17.1-1996 : Elevators | 2.19 - Gears, bearings, and flexible couplings | 1001.2(b)(17) | Yes | No | Seal on machine is leaking excessively and is causing oil to leak down on top of car top, needs to be replaced. Re-inspection required | 5/16/2023 |
| A17.1-1996 : Elevators | 3.20 - Governor rope | 1001.2(c)(26) | Yes | No | Excessive rouging on Governor rope, needs to be replaced with in 30 days. Re-inspection required | 5/16/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit & hoistway needs to be cleaned of debris, oil & lint. | 8/19/2024 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Governor rope has excessive rouging and needs replaced | 9/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Elevator car top needs to be cleaned | 8/19/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Clean debris and dirt from elevator hoistway | 8/19/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Replace leaking seal on elevator traction machine | 8/19/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Elevator cartop needs to be cleaned | 9/13/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Need to clean debris and dirt from elevator hoistway | 9/13/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | Need to replace leaking seal on elevator traction machine | 9/13/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Missing ceiling tiles inside elevator. Take corrective action as needed. | 1/23/2025 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 212 | Yes | No | Hoist ropes are undersized and rouged and meet the criteria for replacement. Take corrective action as needed. | 1/17/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Emergency power was tested and elevator will not take calls, stuck in lobby. Take corrective action and re-test. | 1/17/2025 |
| A17.1-2016 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.4.11 Runby (Re-Inspect) | Yes | No | Ropes need to be shortened, counterweight run by is not sufficient, minimum 6". | 1/17/2025 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | There are 2 phase I fire service key switches at the main lobby landing hall call buttons. The primary switch with bypass, off and on is not functioning. The 2nd switch with off and on only, does recall the elevator to the main lobby landing. Repair non functional phase I key switch. Also call cancel and hold function does not work on phase II fire service, needs repaired. Re-inspection required | 6/25/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Performed test to check elevator on emergency power. After the elevator was transferred to emergency power, the elevator would not run. All operating parameters were lost in elevator controller. Repair elevator to transfer seamlessly to operate on emergency power. Re-inspection required | 6/25/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Performed test to check elevator on emergency power. After the elevator was transferred to emergency power, the elevator would not run. All operating parameters were lost in elevator controller. Repair elevator to transfer seamlessly to operate on emergency power. Re-inspection required | 8/17/2026 |