Inspection
Inspection Details
Equipment ID
17808
17808
Inspection Date
12/19/2024
12/19/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Wright
Michael Wright
Mechanic Name
Anthony Henthorne
Anthony Henthorne
Relief Valve Pressure
N/A
N/A
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
20
20
External ID
0b0fa416-2af7-4646-8703-0e0a55d5090e
0b0fa416-2af7-4646-8703-0e0a55d5090e
Location
Hill Parking Structure
800 Block East 24th St Terr, Kansas City, MO
Phone: (816) 235-1363
Email: cfmaccounting@umkc.edu
800 Block East 24th St Terr, Kansas City, MO
Phone: (816) 235-1363
Email: cfmaccounting@umkc.edu
Owner
Attn: Robert Wren
UMKC- Campus Facilities Mgmt
1011 E 51st St, Kansas City, MO 64110
Phone: (816) 235-1363
Email: rwren@umkc.edu
UMKC- Campus Facilities Mgmt
1011 E 51st St, Kansas City, MO 64110
Phone: (816) 235-1363
Email: rwren@umkc.edu
Billing
Attn: Marc Bates
UMKC- Campus Facilities Mgmt
1011 E 51st St, Kansas City, MO 64110
Phone: (816) 235-1363
Email: batesmw@umkc.edu
UMKC- Campus Facilities Mgmt
1011 E 51st St, Kansas City, MO 64110
Phone: (816) 235-1363
Email: batesmw@umkc.edu
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | perform and post monthly fire service test log in the elevator machine room | 1/20/2021 | ||
| A17.1-1996 : Elevators | 3.26 - Broken rope, chain, or tape switch | 209.2c(2) | x | Coated steel belt monitor is showing errors on several belts, repair belt monitor | 11/2/2020 | |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | the copy of the state operating certificate in the machine room is to be updated annually | 1/20/2021 | ||
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(j) | machine room fire extinguisher is to be inspected and tagged annually | 1/20/2021 | ||
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.11.2.1.3(cc) | the hoist belt monitor is showing an error, the belts tested good, replace faulty belt monitor | 1/20/2021 | ||
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection) | the fire hat light in the car operating panel did not come on during the fire service test | 1/20/2021 | ||
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.11.2.1.3(cc) | x | The coated steel belt monitor is flashing an error, repair/reset the belt monitor verify that the belts test good | 11/14/2022 | |
| A17.1-2016 : Elevators | 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) | 8.11.2.1.2(nn) | tried to trip the seismic and it would not trip, repair and retest | 11/21/2025 | ||
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.6.3.2 (Re-Inspection) | x | coated steel belt monitor is flashing an error, test the belts, if good reset the monitor, if bad replace the hoist belts (8.6.3.2.3) | 11/8/2023 | |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | machine room fire extinguisher does not have an inspection tag, have the extinguisher inspected and tagged annually | 11/21/2025 | ||
| A17.1-2016 : Elevators | 3.34 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) | 8.6.4.19.17 Earthquake Operation | x | could not get the seismic to trip, repair and retest (8.6.4.19.17) | 11/8/2023 | |
| A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 102.1 | the junction box and conduit for the pit stop switch, buffer switch, tail sheave switch is rusted in half and wires are exposed in a couple of places, replace rusted out conduit and junction box (2.8.2.1) | 11/21/2025 | ||
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.6.4.19.13 Broken Suspension Member and Residual Strength Detection Means | x | Belt monitor for the hoist belts is flashing an error on the new hoist belts that were installed, repair belt monitor | 12/19/2024 | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | State operating certificate in the machine room expired in 2011, update with current state operating certificate when received | 11/21/2025 | ||
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | Provide machine room fire extinguisher | 11/21/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | The emergency phone is not working. | 11/21/2025 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Repaired the emergency phone. |