Inspection
Inspection Details
Equipment ID
15604
15604
Inspection Date
12/17/2024
12/17/2024
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Dequarius Millett
Dequarius Millett
Mechanic Name
Thomas Suedkamp
Thomas Suedkamp
Relief Valve Pressure
N/A
N/A
Slide
N/A
N/A
Governor Rope Pull
100/920
100/920
Door Closing Force
21
21
External ID
735f8ac6-87da-4929-84d1-a8983954d8d9
735f8ac6-87da-4929-84d1-a8983954d8d9
Location
Renaissance Grand Hotel- St. Louis
800 Washington Ave, St. Louis, MO
Phone: (314) 621-9600
800 Washington Ave, St. Louis, MO
Phone: (314) 621-9600
Owner
Attn: Marriott St. Louis Grand
Marriott St. Louis Grand
800 Washington Ave, St. Louis, MO 63101
Phone: (314) 333-2326
Alt Phone: (314) 418-5858
Email: STLMGEngineering@marriott.com
Marriott St. Louis Grand
800 Washington Ave, St. Louis, MO 63101
Phone: (314) 333-2326
Alt Phone: (314) 418-5858
Email: STLMGEngineering@marriott.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 3.8 - Top emergency exit | 204.1e | No | No | Emergency exit hatch switch does not disconnect driving machine power. Repair | 8/21/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the elevator machine room | 8/21/2025 |
| A17.1-1996 : Elevators | 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) | 8.4.10.1.2 - Protection not functioning | Yes | No | Earthquake protection is not working. Re-inspection required | 12/17/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Incomplete 5 year inspection. Still needs buffers smashed, 125% hold , setting safeties, slide recorded, and unintended motion tested. | 3/12/2025 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | Yes | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. This currently is an unsafe condition as temporary means of keeping the machine room space cool has resulted in the equipment being open to the elements. Reinspection is required. | 11/5/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Two-way communication could not be established. Repair/replace this phone for proper operation and passenger safety. Reinspection required. | 11/5/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. | 11/5/2025 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | Yes | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. This currently is an unsafe condition as temporary means of keeping the machine room space cool has resulted in the equipment being open to the elements. Reinspection is required | 5/26/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Two-way communication could not be established. Repair/replace this phone for proper operation and passenger safety. Reinspection required. | 5/26/2026 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | Yes | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. This currently is an unsafe condition as temporary means of keeping the machine room space cool has resulted in the equipment being open to the elements. Reinspection is required |