Inspection
Inspection Details
Equipment ID
16928
16928
Inspection Date
11/26/2024
11/26/2024
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
Adam Seiler
Adam Seiler
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
40/300
40/300
Door Closing Force
20
20
External ID
32972ba6-9c5f-45b4-8634-f7f55bcc68a4
32972ba6-9c5f-45b4-8634-f7f55bcc68a4
Location
Abbey Senior Health
206 N Main St, O'Fallon, MO
Phone: (636) 240-3420 Ext: 129
206 N Main St, O'Fallon, MO
Phone: (636) 240-3420 Ext: 129
Owner
Attn: Rudy Semar
Abbey Senior Health
206 N Main St, O'Fallon, MO 63366
Phone: (636) 240-5754
Email: rsemar@abbeyseniorhealth.com
Abbey Senior Health
206 N Main St, O'Fallon, MO 63366
Phone: (636) 240-5754
Email: rsemar@abbeyseniorhealth.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide code compliant maintenance control program documents. | 1/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.7.1.8 | No | No | Provide a code compliant code data tag. | 1/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.19 - Gears, bearings, and flexible couplings | 8.6.1.6.2 | No | No | Verify the oil level in the hoist machine. | 1/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 8.11.2.1.5(j) | Yes | Yes | The following items still need to be tested for completion of Category 5 Test: Set the car safeties, test ascending car over speed, and confirm proper operation of load weighing device. | 11/18/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.19 - Gears, bearings, and flexible couplings | 8.11.2.1.2(q) | No | No | Determine condition of hoist machine bearings and gears. Machine is making loud noise when running down with capacity load. | 1/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.18 - Traction drive machines | 8.11.2.1.2(p) | Yes | No | Controller is indicating 125% load when car is loaded at capacity. | 1/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall be operational. | 2/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | No | Phase 2 fire service not operating properly. | 2/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/1/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | The in-car emergency lights shall be operational. | 4/3/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) | Yes | No | The door open button in the firefighters phase two panel is intermittently sticking in the actuated position and shall be repaired or replaced. | 4/3/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/1/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.2 | Yes | No | Rope shall be shortened for proper runby. | 10/14/2025 |