Inspection
Inspection Details
Equipment ID
21350
21350
Inspection Date
12/9/2024
12/9/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
Jeffrey Miller
Jeffrey Miller
Relief Valve Pressure
640
640
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
19
19
External ID
4340838d-aec9-405b-9c4b-2edc2e56b51b
4340838d-aec9-405b-9c4b-2edc2e56b51b
Location
Elizabeth House
12284 De Paul Dr, Bridgeton, MO
Phone: (314) 412-5019
12284 De Paul Dr, Bridgeton, MO
Phone: (314) 412-5019
Owner
Attn: The Sarah Community
The Sarah Community
12284 De Paul Dr, Bridgeton, MO 63044
Phone: (314) 209-8814
Email: cwhite@thesarahcommunity.org
The Sarah Community
12284 De Paul Dr, Bridgeton, MO 63044
Phone: (314) 209-8814
Email: cwhite@thesarahcommunity.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.3 Guards Between Adjacent Pits | No | No | The pit light shall work. | 10/28/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.3 Guards Between Adjacent Pits | No | No | Remove fluids from the pit. | 10/28/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.11 - Plunger and Cylinder | 3.18 | No | No | The left hydraulic jack packing is worn and leaking. Repair or replace as needed. | 10/29/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate. | 10/29/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/14/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an overspeed valve. A category 5 test shall be performed on the overspeed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. | 10/14/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 12/28/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency power must be tested annually. (2nd Notice) | 9/9/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | Battery lowering unit has been removed and shall be replaced or a variance applied for. See MO Memorandum 016 for more details. | 5/7/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency power operation shall be tested. | 5/7/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/14/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | The ventilation fan is not working. Must repair or replace. | 10/14/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Unit recalled on battery lowering but did not switch to generator power. Elevators equipped to operate on generator power shall be tested annually. | 10/14/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency phone shall establish 2-way communication. |