Inspection
Inspection Details
Equipment ID
10495
10495
Inspection Date
12/18/2024
12/18/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
25
25
External ID
78259275-8ffd-49c4-baf7-c6ece4c09319
78259275-8ffd-49c4-baf7-c6ece4c09319
Location
Salus Center
3545 Lafayette Ave, St. Louis, MO
Phone: (314) 977-2954
3545 Lafayette Ave, St. Louis, MO
Phone: (314) 977-2954
Owner
Attn: Alex Del Vecchio
St. Louis University
3545 Lindell Blvd, 2nd Fl, St. Louis, MO 63103
Phone: (314) 977-2966
Email: alexander.delvecchio@slu.edu
St. Louis University
3545 Lindell Blvd, 2nd Fl, St. Louis, MO 63103
Phone: (314) 977-2966
Email: alexander.delvecchio@slu.edu
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Suspension ropes are undersized, replacement required within 30 days. | 3/30/2022 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | x | Suspension ropes need to be shortened. There is only 3 inches of c-measurement, needs to be a minimum of 6". Re-inspection required | 4/12/2022 | |
MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | x | x | Car safeties did not reach minimum amount of slide required for a 350 fpm car. Unit has been Red-Tagged, Re-inspection required | 4/12/2022 |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | x | Suspension ropes needs to be shortened. There is only 3" of c-measurement, needs to be 6". Re-inspection required | 4/12/2022 | |
MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | x | x | Car safeties did not reach minimum amount of slide required for 350 lb car. Unit is still red tagged | 4/12/2022 |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Replace BC fire extinguisher in machine room with a ABC fire extinguisher | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | x | Shorten hoist cables, car not making it to the top final when the counterweight buffer is fully compressed | 1/8/2024 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | x | Elevator car door restrictor inoperable. Re-inspection required | 12/18/2024 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Need to replace BC extinguisher in the elevator machine room with an ABC | |||
MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Need to shorten hoist cables, car not making it to the top final when counterweight buffer is fully compressed. Re-inspection required | 12/18/2024 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Need to re-program emergency phone, it calls an inactive number. Re-inspection required | ||
MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Need to shorten hoist cables, car not making it to the top final when counterweight buffer is fully compressed. Re-inspection required | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | x | Elevator car door restrictor inoperable, needs to be repaired or replaced. Re-inspection required |