Inspection
Inspection Details
Equipment ID
16131
16131
Inspection Date
1/3/2025
1/3/2025
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
Na
Na
Slide
23”
23”
Governor Rope Pull
80/800
80/800
Door Closing Force
20/20
20/20
External ID
cbfa986a-37a8-44bf-a539-52bd84a3c9b0
cbfa986a-37a8-44bf-a539-52bd84a3c9b0
Location
Tower at OPOP
411 N 8th St, St. Louis, MO
Phone: (314) 621-5443
411 N 8th St, St. Louis, MO
Phone: (314) 621-5443
Owner
Attn: STL Tower
STL Tower Partners, LLC
411 N 8th St, St. Louis, MO 63101
Phone: (314) 621-5443
Alt Phone: (314) 954-8197
STL Tower Partners, LLC
411 N 8th St, St. Louis, MO 63101
Phone: (314) 621-5443
Alt Phone: (314) 954-8197
Billing
Attn: Tower at OPOP leasing office
Tower at OPOP leasing office
411 N 8th St, St. Louis, MO 63101
Phone: (314) 621-5443
Email: jwhite@jstreetps.com
Tower at OPOP leasing office
411 N 8th St, St. Louis, MO 63101
Phone: (314) 621-5443
Email: jwhite@jstreetps.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | No | No | Repair machine room door. | 2/12/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 8.11.2.1.1(o) | No | No | The 14th call button tag has been removed on the car operating panel. Reinstall call button tag for proper identification for passengers. | 2/12/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | No | No | The elevator machine room cannot be used for storage. Remove the inoperable HVAC units being stored in the machine room to provide proper room for maintenance to be performed. | 1/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.7 Firefighters' Emergency Operation: Operating Procedures | No | No | The “Fireman’s Service Phase I” signage is not located at the primary landing adjacent to the Fireman’s Service Phase I key switch as required. Reinstall signage to comply with ASME A17.1 2004. | 2/12/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.9 Elevator Corridor Call Station Pictograph | No | No | The pictograph signage for “In Case of Fire” is missing at multiple elevator landings. Reinstall signage that conforms to the ASME A17.1 2004a that this elevator was designed to conform to. | 2/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | The “smoke guard” barrier device, that was installed on a number of hoistway door landings, has been activated and not reset properly. The device has been temporarily held up by a piece of PVC piping rendering it inoperable in case of an actual emergency. Repair and reset all “smoke guard” barrier devices to operate as designed. | 2/12/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | Yes | No | Provide machine room door to be repaired or replaced. | 2/12/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 8.11.2.1.1(o) | Yes | No | Provide missing braille/tactile plate on COP for 14th floor. | 2/12/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | Yes | No | Remove all non working equipment (air conditioner) from the elevator machine room. | 2/12/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.7 Firefighters' Emergency Operation: Operating Procedures | Yes | No | Post Phase I instructions. | 2/12/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.9 Elevator Corridor Call Station Pictograph | Yes | No | Numerous floors missing lobby warning placards. | 2/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Yes | No | The drop down smoke barriers above each landing are disabled/ not working. | 2/12/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide testing of the elevator on emergency power. | 2/12/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.12 - Standby power selection switch | 2.27.2 | Yes | No | Provide testing of the elevator emergency power selector switch. | 2/12/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.1.1 | No | No | Seal wall penetration around sprinkler pipe in the elevator machine room. | 2/12/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Provide phone to work properly. | 2/12/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.20 | Yes | No | Belt monitor indicator showing bad belt. | 2/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | Clean the machine room. | 2/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Clean the car top. | 2/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Clean th pit. | 2/12/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)4 | No | No | Gap between door and the return are excessive. | 2/12/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 2/12/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | No | No | Provide machine room door to be repaired or replaced. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 8.11.2.1.1(o) | No | No | The 14th call button tag has been removed on the car operating panel. Reinstall call button tag for proper identification for passengers. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.7 Firefighters' Emergency Operation: Operating Procedures | No | No | The “Fireman’s Service Phase I” signage is not located at the primary landing adjacent to the Fireman’s Service Phase I key switch as required. Reinstall signage to comply with ASME A17.1 2004. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.9 Elevator Corridor Call Station Pictograph | No | No | The pictograph signage for “In Case of Fire” is missing at multiple elevator landings. Reinstall signage that conforms to the ASME A17.1 2004a that this elevator was designed to conform to. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | The “smoke guard” barrier device, that was installed on a number of hoistway door landings, has been activated and not reset properly. The device has been temporarily held up by a piece of PVC piping rendering it inoperable in case of an actual emergency. Repair and reset all “smoke guard” barrier devices to operate as designed. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 8.11.2.1.1(o) | No | No | Provide missing braille/tactile plate on COP for 14th floor. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Remove all non working equipment (air conditioner) from the elevator machine room. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.7 Firefighters' Emergency Operation: Operating Procedures | No | No | Post Phase I instructions. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.9 Elevator Corridor Call Station Pictograph | No | No | Numerous floors missing lobby warning placards. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The drop down smoke barriers above each landing are disabled/ not working. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide testing of the elevator on emergency power. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.12 - Standby power selection switch | 2.27.2 | No | No | Provide testing of the elevator emergency power selector switch. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.1.1 | No | No | Seal wall penetration around sprinkler pipe in the elevator machine room. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Provide phone to work properly. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Machine room shall be kept clean and free of all non-evlevator materials. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Clean the pit. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | Clean the car top. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)4 | No | No | Gap between door and the return are excessive. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. |