Inspection
Inspection Details
Equipment ID
4756
4756
Inspection Date
12/16/2024
12/16/2024
Inspection Type
Reinspection
Reinspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Christian Schickedanz
Christian Schickedanz
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
04879766-e39d-4343-9208-ee2237f95ade
04879766-e39d-4343-9208-ee2237f95ade
Location
MO Baptist Medical Center-Bldg C
3009 N Ballas Rd, St. Louis, MO
Phone: (314) 996-5346
3009 N Ballas Rd, St. Louis, MO
Phone: (314) 996-5346
Owner
Attn: BJC C/O Cushman And Wakefield Eager Rd
BJC C/O Cushman And Wakefield Eager Rd
3009 N Ballas Rd, St. Louis, MO 63131
Phone: (000) 000-0000
BJC C/O Cushman And Wakefield Eager Rd
3009 N Ballas Rd, St. Louis, MO 63131
Phone: (000) 000-0000
Billing
Attn: BJC C/O Cushman And Wakefield Eager Rd
BJC C/O Cushman And Wakefield Eager Rd
8300 Eager Rd, Ste 600, St. Louis, MO 63144
Phone: (314) 996-5346
Email: bjcinvoices@cushwake.com
BJC C/O Cushman And Wakefield Eager Rd
8300 Eager Rd, Ste 600, St. Louis, MO 63144
Phone: (314) 996-5346
Email: bjcinvoices@cushwake.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 12/19/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. Note: The certificate expired in 2021. | 11/14/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | The auxiliary power lowering operation shall be functional. | 10/6/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | The overspeed valve shall be tested with rated load. Note: The last test was in 2017. | 10/6/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Relief valve setting to be adjusted above full load pressure (280 psi), not to exceed 125% of same. | 10/9/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | Overspeed valve to be tested, sealed and tagged. Testing shall be completed within 90 days. | 10/9/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | No | No | Fire service buzzer and fire hat shall work correctly. | 11/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communications loss monitor shall work. | 10/9/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Compliant/required documentation & MCP shall be kept in equipment room (neat/organized) including wiring diagrams, PM log, callback log, evacuation procedures, oil log, and fire service log, recorded monthly. | 11/14/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. Remove excess debris. | 11/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Adjust upthrust roller bearings for proper clearance to door hanger track (multiple floors). | 11/14/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | This elevator is equipped with an overspeed valve. A category 5 test shall be performed on the overspeed valve immediately. The overspeed valve was last tested in 2017. Unit will be red tagged and locked out of service if not tested. | 12/16/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean and free from dirt and rubbish. | 11/14/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | Yes | No | Fire service buzzer does not work. | 12/16/2024 |