Inspection
Inspection Details
Equipment ID
13987
13987
Inspection Date
12/20/2024
12/20/2024
Inspection Type
Reinspection
Reinspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Matthew Toettcher
Matthew Toettcher
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
fb78e4f5-1adb-4699-8f2d-d54bd07435e4
fb78e4f5-1adb-4699-8f2d-d54bd07435e4
Location
Coronado Place
3701 Lindell Blvd, St. Louis, MO
Phone: (918) 575-0716
3701 Lindell Blvd, St. Louis, MO
Phone: (918) 575-0716
Owner
Attn: St. Louis Properties
St. Louis Properties
3701 Lindell Blvd, St. Louis, MO 63108
Phone: (314) 931-2732
Email: coronadoplacemgr@greystar.com
St. Louis Properties
3701 Lindell Blvd, St. Louis, MO 63108
Phone: (314) 931-2732
Email: coronadoplacemgr@greystar.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Repair inoperable emergency phone. | 4/17/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Replace earthquake halo on counterweight frame. | 4/15/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working. | 4/15/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work on 110v emergency power or normal power. Repair or replace | 11/27/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Elevator car top shall remain clean to prevent any hazards | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Elevator pit shall be clean of all debris | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Elevator pit light shall work with a minimum of 5 foot candles. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Up to date operating certificate is required in the machine room. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room lighting shall work. No less than 10 foot candles at floor level. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Missing junction box covers on fire service wiring. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Basement hall button plate needs to be mounted securely. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | "In case of fire" pictograph is missing at call stations. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Basement Braille tag is missing. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Re-install the cover on the open air vent by the elevator equipment. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work. | 12/20/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | Yes | No | Lockable disconnect required. Circuit breaker shall be lockable. | 12/20/2024 |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 8.6.4.20.2 | Yes | Yes | The maximum tripping speed for the governor is 452 fpm. It is not tripping until 500 fpm. Elevator Red Tagged. | 12/20/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | Yes | No | Lockable disconnect required. Circuit breaker shall be lockable. (Not corrected as of 12/20/24 re-inspection) | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work. (Not corrected as of 12/20/24 re-inspection) |