Inspection
Inspection Details
Equipment ID
17772
17772
Inspection Date
1/13/2025
1/13/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas Krug
Thomas Krug
Mechanic Name
Walter Tauchert
Walter Tauchert
Relief Valve Pressure
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
19
19
External ID
60f67173-4937-4e5a-99c2-9b9357dcf5fd
60f67173-4937-4e5a-99c2-9b9357dcf5fd
Location
Bee Hat Apartments
1021 Washington Ave, St. Louis, MO
Phone: (000) 000-0000
1021 Washington Ave, St. Louis, MO
Phone: (000) 000-0000
Owner
Attn: Bee Hat Apartments
Bee Hat Apartments
1021 Washington Ave, St. Louis, MO 63101
Phone: (314) 371-0035 Ext: 202
Bee Hat Apartments
1021 Washington Ave, St. Louis, MO 63101
Phone: (314) 371-0035 Ext: 202
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Emergency light in car doesn't work | 7/13/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Standing water in pit. Sump pump bot working | 6/5/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone fails to dial out | 6/7/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | -A written Maintenance Control Program shall be in place to maintain the equipment in compliance with the requirements of Section 8.6. | 6/5/2026 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.11.2.1.5(a) | No | No | Electrical Piping to car buffer is rusted away. Buffer switch wiring is exposed on pit floor. | 6/5/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency Phone in car fails to establish two-way communication | 1/13/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | There is 4 inches of water in the pit. The sump pump is not working. All pits shall be kept clean and dry | 6/5/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | The sump hole cover has corroded to the point that it is broken in half. All sump holes shall be provided with a cover | 6/5/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The pit light is not functioning. | 6/5/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The sump pump is not functioning. Means shall be provided to prevent the accumulation of water in elevator pits. | 6/5/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | The large penetration in the hoistway wall where the sump pump piping is ran into the pit needs to be sealed. | 6/5/2026 |