Inspection
Inspection Details
Equipment ID
1122
1122
Inspection Date
12/12/2018
12/12/2018
Inspection Type
Reinspection
Reinspection
Inspector Name
Gerald Glynn
Gerald Glynn
Mechanic Name
Glenn Everhart
Glenn Everhart
Relief Valve Pressure
490
490
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
24f7b6cf-3bf1-45f2-bec1-19f4c58fd9be
24f7b6cf-3bf1-45f2-bec1-19f4c58fd9be
Location
JCK Library
415 E CLARK ST, WARRENSBURG, MO
415 E CLARK ST, WARRENSBURG, MO
Owner
Attn: University of Central Missouri
University of Central Missouri
116 S, CLARK ST, WARRENSBURG, MO 64093
Phone: (000) 000-0000
Email: fpo_bus_ops@ucmo.edu
University of Central Missouri
116 S, CLARK ST, WARRENSBURG, MO 64093
Phone: (000) 000-0000
Email: fpo_bus_ops@ucmo.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Emergency phone not working no dial tone | 9/17/2018 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)1 | No | No | elevator settling 2 1/2" in 15 min-shut machine room valve--no settling-oil leaking back thru control balve. Repair or replace | 9/17/2018 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State certifiate in machine room | 8/28/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Oil tank lid ahould be modified to provide safe access by maintenance personnel to valve and pump and prevent damage to oil coolers. 120v outlet to power oil coolers on # 2 nonfunctional | 8/27/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State certificate in machine room | 8/27/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | In case of fire don't use elevator signage needed | 9/3/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | In case of fire don't use elevator signage needed | 11/22/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | missing "in case of fire" sign at lobby | 11/22/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | No | No | door closing pressure above 30 lbs | 7/6/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 3.26.10 | Yes | No | Emergency battery lowering not working. Batteries | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | MCP needed | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Light bulb burnt out |