Inspection
Inspection Details
Equipment ID
15026
15026
Inspection Date
12/19/2024
12/19/2024
Inspection Type
Reinspection
Reinspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Ronald Hogue, Jr
Ronald Hogue, Jr
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
98bbe629-fa39-4f6f-a979-3e88429c0b0f
98bbe629-fa39-4f6f-a979-3e88429c0b0f
Location
Hidden Lake Care Center
11750 Hidden Lake Dr, St. Louis, MO
Phone: (314) 355-5153
11750 Hidden Lake Dr, St. Louis, MO
Phone: (314) 355-5153
Owner
Attn: Hidden Lake Care Center
Hidden Lake Care Center
11750 Hidden Lake Dr, St. Louis, MO 63138
Phone: (000) 000-0000
Email: swooten@estatesofhiddenlake.com
Hidden Lake Care Center
11750 Hidden Lake Dr, St. Louis, MO 63138
Phone: (000) 000-0000
Email: swooten@estatesofhiddenlake.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate. | 11/21/2018 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational with 24/7 support. | 11/4/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display a copy of the current state operating certificate. | 3/15/2024 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 3/15/2024 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 3/15/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/15/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | Evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 3/15/2024 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. | 3/15/2024 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) | Yes | No | The overspeed valve is not sealed and has been previously cited that a category 5 test is needed. A category 5 test shall be performed within 90 days. | 2/27/2024 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | The machine room lights shall be repaired. | 3/15/2024 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | The machine room lights shall be guarded. | 3/15/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | The in-car stop switch shall not be rendered inoperative on phase one fire service until the car is in motion. | 2/27/2024 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 2/27/2024 |
| A17.1-1996 : Elevators | 2.14 - Code data plate | 215 | No | No | The code data plate required by A17.1 2013, 2016 8.9 shall be provided in plain view, securely attached to each main line disconnect or controller. | 3/15/2024 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | The data on the MCP shall be filled out as required by A17.1 2016 8.6.1.4.1(a)(3). | 3/15/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The fire service phase one key-switch bezel shall be legible. | 3/15/2024 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) | Yes | No | A category 5 test of the overspeed valve shall be performed within 90 days. | 3/15/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Phase II fire service shall be operational. 14 days to correct violation or unit will be red tagged and locked out of service. | 12/19/2024 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 207.8 | Yes | No | Emergency power must be tested annually. | |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | Fire extinguisher is out dated. | |
| A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(5) Oil Leakage Collection | No | No | A means of collecting oil from the plunger head and the packing must be provided in the pit. It may not exceed 5 gallons. | |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 102 | Yes | No | The sump pump in the pit shall work. | |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Pit floor may not have hydrualic oil on it. |