Inspection
Inspection Details
Equipment ID
6947
6947
Inspection Date
1/21/2025
1/21/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Raymond Stidham
Raymond Stidham
Mechanic Name
Clarence Bailey, Jr.
Clarence Bailey, Jr.
Relief Valve Pressure
450
450
Slide
Governor Rope Pull
Door Closing Force
19
19
External ID
675a8dcd-1884-4207-8ee0-2205d9a15a55
675a8dcd-1884-4207-8ee0-2205d9a15a55
Location
Lamplighters Inn
1772 S Glenstone Ave, Springfield, MO
Phone: (417) 830-6297
1772 S Glenstone Ave, Springfield, MO
Phone: (417) 830-6297
Owner
Attn: Elliott Lodging
Elliott Lodging
1736 E Sunshine St, Ste 1011, Springfield, MO 65804
Phone: (000) 000-0000
Email: phil@elliottlodging.com
Elliott Lodging
1736 E Sunshine St, Ste 1011, Springfield, MO 65804
Phone: (000) 000-0000
Email: phil@elliottlodging.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Obtain and display a current state operating certificate in the machine room. | 5/21/2020 |
| conversion | conversion | n/a | No | No | Provide a 6 foot high chain link fence around the elevator equipment with a 36 inch wide gate that is always locked from the outside and never locked from the inside, it is to be self closing self latching. maintain a minimum of 36 inches clear working area in front of the equipment. | 5/21/2020 |
| conversion | conversion | n/a | No | No | Clean up the pit. | 5/21/2020 |
| conversion | conversion | n/a | No | No | Provide phase 1 fire instructions at the primary landing | 5/21/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Replace the burnt out light tubes in the light fixture above the controller in the machine room | 5/21/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room. This was on last years inspection too. | 5/21/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Provide a 6 foot high chain link fence seperating the elevator equipment from the other building related equipment. I t is to be provided with a 3 foot wide gate with a self closing and self latching, locking system. This was on last years inspection too. | 5/21/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Replace the burnt out pit light. | 5/21/2020 |
| A17.1-2016 : Elevators | 1.15 - sign and operating device symbols | 8.6.1.6.7 | No | No | No-- Do Not Use Elevator in CASE OF FIRE signs posted | 2/9/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(b) On-Site Maintenance Records (Repair and Replacement Records) | No | No | NO records | 2/9/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)1 | Yes | No | Back of cab needs refastened.. | 3/20/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | Yes | No | Clean Machine Room | 3/20/2023 |