Inspection
Inspection Details
Equipment ID
1747
1747
Inspection Date
1/20/2025
1/20/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
20 / 23
20 / 23
External ID
84ef65e5-4149-4846-a493-9a92a9d7e353
84ef65e5-4149-4846-a493-9a92a9d7e353
Location
St. Louis Altenheim
5408 S Broadway, St. Louis, MO
Phone: (314) 353-7225
5408 S Broadway, St. Louis, MO
Phone: (314) 353-7225
Owner
Attn: Jean Bardwell - Administrator
St. Louis Altenheim
5408 S Broadway, St. Louis, MO 63111
Phone: (314) 353-7225
Email: rpatterson@stlaltenheim.com
St. Louis Altenheim
5408 S Broadway, St. Louis, MO 63111
Phone: (314) 353-7225
Email: rpatterson@stlaltenheim.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.1 | Yes | No | Counterweight runby is 1". Minimum required is 6" | 4/16/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | PHONE SHALL ALLOW FOR 2-WAY COMMUNICATION. | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | EMERGENCY LIGHTING SHALL WORK WITH LOSS OF MAIN 120v POWER. | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually. | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.6.2.5 | Yes | No | Shorten Hoist Ropes. Where spring buffers are used, bottom runby shall be not less than 6". | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | Machine room door shall be self-closing and self-locking . Door does not latch. | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | No | No | Machine room lighting needs to be repaired, 1 or more bulbs not working. | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Machine Room shall have proper Fire Extinguisher and shall have current monthly/annual test tag. (Expired) | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Fire Service Testing must be documented monthly. The form is present in the MCP, but hasn't been logged monthly. | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 Door Systems | Yes | No | Hoistway door has loose guide on 2R floor. Repair/replace as needed. | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.20 | No | No | Hoist Ropes are dry and showing “rouge” and "dusting" on floor. Ropes shall be cleaned and lubricated per OEM recommendations | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.7 - Car door or gate | 2.14.4 | No | No | Adjust upthrust roller bearings for proper clearance to door hanger track.(all floors). | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.6.2.5 | Yes | No | Shorten Hoist Ropes. Where spring buffers are used, bottom runby shall be not less than 6". | 8/31/2026 |