Inspection
Inspection Details
Equipment ID
21016
21016
Inspection Date
1/14/2025
1/14/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Jarod Watson
Jarod Watson
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
13
13
External ID
105be65d-42d1-43d4-959c-b5805d372c3d
105be65d-42d1-43d4-959c-b5805d372c3d
Location
1618 Tower Grove LLC
1618 Tower Grove Ave, St. Louis, MO
Phone: (314) 664-7646
1618 Tower Grove Ave, St. Louis, MO
Phone: (314) 664-7646
Owner
Attn: 1618 Tower Grove LLC
1618 Tower Grove LLC
1618 Tower Grove Ave, St. Louis, MO 63110
Phone: (314) 664-7646 Ext: 196
Email: lauren.zhao@citygardenschool.org
1618 Tower Grove LLC
1618 Tower Grove Ave, St. Louis, MO 63110
Phone: (314) 664-7646 Ext: 196
Email: lauren.zhao@citygardenschool.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | The in car emergency lighting shall be operational. | 2/11/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display a current MO state operating certificate in the elevator machine room. | 3/12/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide a code compliant MCP including onsite documents. | 3/12/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 3/2/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | The hoistway doors are missing the middle hanger. | 3/2/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | The hoistway doors are missing the middle fire gib. | 3/2/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | The pit shall be kept dry. | 10/26/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | There is a pipe on the front pit wall discharging water into the pit. The pipe shall be removed or sealed. | 10/26/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | The receptacle in the machine room shall be a GFCI. | 10/26/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.22 - Wire rope fastening and hitch plate | 8.11.2.1.3(bb) | Yes | No | The suspension rope clip shall be properly spaced. | 3/2/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.11.2.1.5(b) | Yes | No | The counterweight runby shall not exceed 6.5 inches. | 3/2/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 10/26/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The wood in the control room shall be removed or painted with an intumescent paint. | 10/26/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | The hoistway doors are missing the middle hanger. | 10/27/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | The hoistway doors are missing the middle fire gib. | 10/27/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.22 - Wire rope fastening and hitch plate | 8.11.2.1.3(bb) | Yes | No | The suspension rope clip shall be properly spaced. | 10/27/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.4.11 | Yes | No | The counterweight runby shall not exceed 6.5 inches. | 10/27/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.11.1 | No | No | Up-to-date wiring diagrams shall be provided and permanently kept in the machine room. There are no schematics on-site. | 1/17/2024 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | No | The governor rope shall be tagged as specified by CSR 40-5.065(L)1. | 1/17/2024 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | No | The suspension ropes shall be tagged as specified by CSR 40-5.065(L)1. | 1/17/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Note: 2022 & 2023 records are blank. | 1/17/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.12 - Controller Wiring, Fuses, Grounding, Etc. | 8.6.1.6.3 | No | No | Up-to-date wiring diagrams shall be provided and permanently kept in the machine room. There are no schematics on-site. | 1/17/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The governor rope shall be tagged as specified by CSR 40-5.065(L)1. | 1/17/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The suspension ropes shall be tagged as specified by CSR 40-5.065(L)1. | 1/17/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.20 | No | No | Suspension rope tail ends shall be properly seized/banded. Electrical tape is not proper. | 1/17/2024 |