A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
Yes
|
Yes
|
The heat detector in the overhead shall be removed. There is a heat and a smoke sensor in the overhead, but no sprinkler in the overhead.
|
11/26/2024
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.8
|
Yes
|
No
|
2.8.3.3.4 - The electrical equipment in the pit located less than 48" above the floor (except earthquake protective devices) shall be weatherproof, and the wiring (except travel cables) shall be identified for use in wet locations.
|
11/26/2024
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
3.1
|
Yes
|
No
|
The overhead fasteners protruding through the ceiling of the overhead shall be cut off flush to prevent a hazardous situation.
|
11/26/2024
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
3.1
|
Yes
|
No
|
The hole in the hoistway wall for the sump pump discharge pipe must be filled with approved material.
|
11/26/2024
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3
|
Yes
|
Yes
|
Fire service operation and all initiation devices shall be tested.
|
11/26/2024
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.5 Sump Pump Required/Capacity (Re-Inspect)
|
Yes
|
No
|
The pit sump pump must be operational. The pump was turning on without the presence of water during the test, and wouldn't turn off.
|
11/26/2024
|
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2
|
Yes
|
No
|
A separate branch circuit shall supply the car lights, receptacles, auxiliary lighting power source, and ventilation on each elevator car. Note: One of the pit lights are on the same branch circuit as the car lights. Also the pit light switch will only turn off one of the two lights in the pit. These items shall be corrected.
|
11/26/2024
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
Yes
|
No
|
In electrical equipment rooms, the illumination shall not be controlled by automatic means only. In the elevator machine room, this switch is currently a motion sensor.
|
11/26/2024
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
3.27.2 Phase I Emergency Recall Operation Prior to Device Actuation
|
Yes
|
Yes
|
The machine room heat detector failed to activate the shunt trip disconnect.
|
1/14/2025
|