Inspection
Inspection Details
Equipment ID
19156
19156
Inspection Date
1/30/2025
1/30/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dequarius Millett
Dequarius Millett
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
520
520
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
25
25
External ID
a9668d19-b2dd-4b46-992d-6a9dc6ea9d29
a9668d19-b2dd-4b46-992d-6a9dc6ea9d29
Location
Creamery Apartments
3301 Park Ave, St. Louis, MO
Phone: (314) 446-4528
3301 Park Ave, St. Louis, MO
Phone: (314) 446-4528
Owner
Attn: Creamery Apartments
Creamery Apartments
3301 Park Ave, St. Louis, MO 63104
Phone: (314) 446-4528
Creamery Apartments
3301 Park Ave, St. Louis, MO 63104
Phone: (314) 446-4528
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work. | 2/7/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | Yes | No | Bottom left hand cylinder needs to be looked at. 4" of rust on the bottom cylinder. | 2/7/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams | Yes | Yes | Water is leaking through drywall ceiling into the elevator controller in machine room causing an unsafe condition. Elevator has been Red-tagged and removed form service. Re-inspection required | 10/20/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current operating certificate shall be on display in the machine room | 1/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | High speed down coil on elevator control valve is not being energized, causing elevator to run at leveling speed in the down direction, needs to be repaired | 1/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency lights in elevator cab do not work, needs repair. Re-inspection required | 10/20/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Elevator cab ceiling is missing, leaving fluorescent light bulbs unprotected. Either re-install cab ceiling or guard bulbs against breakage. | 1/27/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 1/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | High speed down coil on elevator control valve is not being energized, causing elevator to run at leveling speed in the down direction, needs repaired. | 1/27/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Elevator cab ceiling is missing leaving fluorescent light bulbs unprotected, Either re-install cab ceiling or guard bulbs against breakage. | 1/27/2026 |