Inspection
Inspection Details
Equipment ID
16584
16584
Inspection Date
2/6/2025
2/6/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James VanZant
James VanZant
Mechanic Name
Clarence Bailey, Jr.
Clarence Bailey, Jr.
Relief Valve Pressure
390
390
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
f2f8274d-83a1-4d45-ba4e-ec4caadb5be1
f2f8274d-83a1-4d45-ba4e-ec4caadb5be1
Location
Q-Hotel
1117 E Saint Louis St, Springfield, MO
Phone: (417) 864-4300
1117 E Saint Louis St, Springfield, MO
Phone: (417) 864-4300
Owner
Attn: Paul
Atrium Hospitality
300 S John Q Hammons Pkwy H#JQ, Springfield, MO 65806
Phone: (417) 862-0070
Email: david.wheeler@atriumhospitality.com
Atrium Hospitality
300 S John Q Hammons Pkwy H#JQ, Springfield, MO 65806
Phone: (417) 862-0070
Email: david.wheeler@atriumhospitality.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | Replace the missing door closer on machine room door.it is to be self closing self latching. | |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Replace the emergency light battery as it is dead | 1/31/2022 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Replace the burnt up sump pump and remove the plywood cover you placed over the pit it has to be metal and it is laying in the pit. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone as there is no dial tone. | 4/11/2023 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Replace the emergency light battery. | 4/11/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room | |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 1001.2(b)(6) | No | No | Re-install the missing fire damper in the HVAC VENT pipe on the machine room ceiling. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room | |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Have the fire extinguisher re-certified | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Have the emergency phone repaired as it has no dial tone | 2/6/2025 |