Inspection
Inspection Details
Equipment ID
20495
20495
Inspection Date
11/13/2018
11/13/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
John Ryan
John Ryan
Mechanic Name
Ronnie Morris
Ronnie Morris
Relief Valve Pressure
300
300
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
5c883a61-f912-4301-a104-f4dd806b994f
5c883a61-f912-4301-a104-f4dd806b994f
Location
Express Scripts
8455 UNIVERSITY PLACE DR, SAINT LOUIS, MO
8455 UNIVERSITY PLACE DR, SAINT LOUIS, MO
Owner
Express Scripts Inc
1 EXPRESS WAY, SAINT LOUIS, MO 63121-1824
1 EXPRESS WAY, SAINT LOUIS, MO 63121-1824
Billing
Attn: Express Scripts Inc
8455 UNIVERSITY PLACE DR, SAINT LOUIS, MO 63121-1825
8455 UNIVERSITY PLACE DR, SAINT LOUIS, MO 63121-1825
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display the current state operating certificate. | 4/20/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.11 - Plunger and Cylinder | 3.18 | No | No | The hydraulic jack packing gland is leaking. Make the necessary corrections. | 4/20/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 9/8/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 9/1/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 9/7/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. | 11/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | The emergency/standby power shall be tested. | 10/8/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/21/2025 |