Inspection
Inspection Details
Equipment ID
16715
16715
Inspection Date
1/14/2025
1/14/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kevin Hecht
Kevin Hecht
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
320
320
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
15
15
External ID
5d366db5-f1ed-4889-9e7a-9b6cbf7f7e82
5d366db5-f1ed-4889-9e7a-9b6cbf7f7e82
Location
505 Washington Bldg
505 Washington Ave, St. Louis, MO
Phone: (314) 630-0266
505 Washington Ave, St. Louis, MO
Phone: (314) 630-0266
Owner
Attn: Roberto Chacon
P&F Properties
1167 Hillside Dr, St. Louis, MO 63117
Phone: (314) 220-6725
Email: rchacon@chaconconstruction.com
P&F Properties
1167 Hillside Dr, St. Louis, MO 63117
Phone: (314) 220-6725
Email: rchacon@chaconconstruction.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | Yes | No | A duplex GFCI receptacle shall be provided in the machine room. Note: The machine room receptacle is not a GFCI | 3/2/2023 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 3.27 | Yes | Yes | Spot-type smoke detectors shall be located on the ceiling or, if on a sidewall, between the ceiling and 12 inches down from the ceiling to the top of the detector. Note: The smoke detectors in the elevator lobbies do not meet these requirements. | 3/2/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Permanent lighting shall be installed and so lighted that the illumination at the landing sills, when an elevator is in service, shall be not less than 100 lx (10 fc) Note: All the elevator lobbies are illuminated with temporary lighting. Permanent lighting shall be installed | 3/2/2023 |
| A17.1-2016 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 2.14.1.7.1 | Yes | No | A standard railing conforming to 2.10.2 shall be provided on the outside perimeter of the car enclosure top on all sides where a 12 inch ball can pass between the edges of the car enclosure top and the adjacent hoistway enclosure and on sides where there is no hoistway enclosure. | 3/2/2023 |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 3.8 | Yes | No | Only such electrical wiring used directly in connection with the elevator shall be permitted to be installed inside the hoistway. Note: The unenclosed twisted pair of wires running down from the hoistway overhead, and the truncated flexible raceways, which are also unenclosed at each floor above the entrances do not meet these requirements | 3/2/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2 On-Site Documentation | Yes | No | All the on site documentation required by A17.1 2016 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Note: Please provide a compliant MCP for each elevator | 3/2/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | Yes | No | Up-to-date wiring diagrams for each elevator shall be provided and permanently kept in the machine room. Note: No schematics have been provided | 3/2/2023 |
| A17.1-2016 : Elevators | 1.16 - Rated load, platform area, and data plate | 2.16.3 | Yes | No | A data plate conforming to 2.16.3.2.2 shall be provided on the car-top. | 3/2/2023 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.1 Phase I Emergency Recall Operation | Yes | Yes | Smoke detectors used to initiate Phase I Emergency Recall Operation shall be installed at each elevator lobby served by the elevator. Note: Fire service is presently being initiated by smokes from another elevator lobby not associated with this two car group, and isn't allowed | 3/2/2023 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(c) Stop Switch Inoperable in Fire Service (Re-Inspection) | Yes | No | The COP keyed stop switch, when opened (“STOP” position) shall cause the electric power to be removed from the elevator driving-machine. Note: This switch shall not be rendered inoperative on phase one fire service as it was required to be in A17.1 2005 | 3/2/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | If the telephone line or equivalent means is not functional, an audible and illuminated visual signal shall be activated. Note: The audible signal is not working | 3/2/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.6 Verification of Telephone Operability | Yes | No | A means to silence the audible signal required by 3.27, 2.27.1.1.6 shall be provided and shall be accessible only to authorized personnel. The signal when silenced shall remain silent for a period of no less than 12 hr or until activated by the next failed periodic verification. Note: This couldn't be tested because the audible signal wasn't working | 3/2/2023 |
| A17.1-2016 : Elevators | 3.9 - Floor and emergency identification numbering | 3.29 | Yes | No | The buffers or pit channel in the pit shall have an identification number which is visible from the pit access door landing. | 3/2/2023 |
| A17.1-2016 : Elevators | 1.15 - sign and operating device symbols | 8.6.1.6.7 | Yes | No | A car identification number shall be located adjacent to or on every elevator entrance at the designated level and the alternate level, minimum of 3 inches in height. | 3/2/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Yes | No | A periodic test record containing the applicable Code requirement(s) and date(s) performed, and the name of the person or firm performing the test shall be installed to be readily visible and adjacent to or securely attached to the controller of each unit in the form of a metal tag. | 3/2/2023 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | All holes and penetrations in the hoistway shall be patched and sealed with approved material. | 3/2/2023 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | Yes | No | The machine room shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key. Note: There are two machine room doors, one of which is not self-closing/locking. | 3/24/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.6 Verification of Telephone Operability | Yes | No | Emergency communications loss monitor shall work. | 3/26/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2 On-Site Documentation | No | No | A code compliant MCP and related on-site documentation shall be provided in the machine room. Note: No 2022, and 2023 is blank. | 4/2/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Replace the missing door guide(s). | 4/2/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency two-way communication device shall remain operative when building power is disconnected. | 7/24/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.6 Verification of Telephone Operability | Yes | No | Emergency communications loss monitor shall work. | 7/24/2025 |