Inspection
Inspection Details
Equipment ID
10636
10636
Inspection Date
11/7/2018
11/7/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
John Ryan
John Ryan
Mechanic Name
Raymond Gore
Raymond Gore
Relief Valve Pressure
380
380
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
1e0e5647-7035-4573-88ae-d8d7cdb43a10
1e0e5647-7035-4573-88ae-d8d7cdb43a10
Location
Sherbrook Village
4102 RIPA AVE, SAINT LOUIS, MO
4102 RIPA AVE, SAINT LOUIS, MO
Owner
Alexian Bros Sherbrooke Village
4005 RIPA AVE, SAINT LOUIS, MO 63125-2378
4005 RIPA AVE, SAINT LOUIS, MO 63125-2378
Billing
Attn: Alexian Brothers Sherbrooke Village
4102 RIPA AVE, SAINT LOUIS, MO 63125
4102 RIPA AVE, SAINT LOUIS, MO 63125
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Need copy of current state operating certificate in machine room. | 12/10/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Door restrictor shall work on battery power. | 11/7/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The in car emergency telephone shall be operational. | 12/2/2019 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The relief pressure shall be tested and a 15 minute standing test shall be performed. | 2/4/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency telephone shall be operational. | 10/28/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | On fire service operation, a means shall be provided to cancel registered car calls. | 10/28/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | On fire service operation, a means shall be provided to cancel registered car calls. Customer will need to apply for a variance from the State of Missouri. | 3/21/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency phone shall work. | 2/6/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Up-to-date operating certificate is required in the machine room. | 4/3/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/3/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Yes | No | Car operating panel - top row buttons are damaged and shall be repaired or replaced. | 2/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Car door restrictor shal work at all floors. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell shall work with loss of main 120 V power. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light shall work with loss of main 120v power. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Operating Certificate EXPIRED 10/2023 due to open violations that need to be cleared so that new certificates can be issued. The displayed certificate is 2015-2016. |