Inspection
Inspection Details
Equipment ID
15855
15855
Inspection Date
2/13/2025
2/13/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Tim Crafton
Tim Crafton
Mechanic Name
Brian Heine
Brian Heine
Relief Valve Pressure
580
580
Slide
Governor Rope Pull
Door Closing Force
29
29
External ID
28dcff76-001d-46ad-85f3-b536dcd1d1be
28dcff76-001d-46ad-85f3-b536dcd1d1be
Location
Courtyard by Marriott
400 Broadway St, Cape Girardeau, MO
Phone: (573) 579-1901
400 Broadway St, Cape Girardeau, MO
Phone: (573) 579-1901
Owner
Attn: H & H Center Property, LLC
H & H Center Property, LLC
1610 N Kingshighway, Ste 301, Cape Girardeau, MO 63701
Phone: (573) 579-1901
Email: patty.schaefer@maysoncapital.com
H & H Center Property, LLC
1610 N Kingshighway, Ste 301, Cape Girardeau, MO 63701
Phone: (573) 579-1901
Email: patty.schaefer@maysoncapital.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post the current state operating certificate. | 8/26/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Clean the pit. | 8/26/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Provide a cover on the sump pump. | 8/26/2020 |
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 1001.2(a)(15) | No | No | Provide elevator numbering on the inside of the car. | 8/26/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Provide means for emergency monitoring company to identify correct car number. | 8/26/2020 |
| A17.1-1996 : Elevators | 3.9 - Floor and emergency identification numbering | 1001.2(c)(15) | No | No | Provide numbering of the car top. | 8/26/2020 |
| A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(4) | No | No | Determine the source of the corrosion where the hydraulic supply piping attaches to the cylinder. May be dissimilar metals. Re-Inspection required. | 8/26/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 3/15/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 4/16/2021 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Pits shall be kept free of dirt and rubbish and shall not be used for storage purposes. | 3/25/2026 |
| A17.1-1996 : Elevators | 3.12 - Pipes, wiring, and ducts | 102 | No | No | Electrical box cover plate in pit is missing. | 3/25/2026 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This unit is equipped with an overspeed valve and is due for category 5 testing in 2024. | 3/25/2026 |