Inspection
Inspection Details
Equipment ID
27023
27023
Inspection Date
1/31/2025
1/31/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Jake Brennan
Jake Brennan
Relief Valve Pressure
420
420
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
15
15
External ID
875fd879-8207-4d48-b66a-52fd642e4773
875fd879-8207-4d48-b66a-52fd642e4773
Location
Liguori Publications
200 Liguori Drive, Liguori, MO
Phone: (636) 464-2500
200 Liguori Drive, Liguori, MO
Phone: (636) 464-2500
Owner
Attn: Redemptorist Fathers doing business as Liguori Publications
Redemptorist Fathers doing business as Liguori Publications
200 Liguori Drive, Liguori, MO 63057
Phone: (636) 464-2500
Email: jgantz@liguori.org
Redemptorist Fathers doing business as Liguori Publications
200 Liguori Drive, Liguori, MO 63057
Phone: (636) 464-2500
Email: jgantz@liguori.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | Yes | No | Main line disconnect to be moved. Currently over the pump unit flush to the wall next to the controller. There is no working clearance. | 1/31/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Machine room smoke detector needs to be relocated to a code compliant location. | 1/31/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Machine room door shall be fire rated and shall be self-closing and self-locking. | 1/31/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Yes | No | There are leaky joints on hydraulic line. Take corrective action as needed. | 1/31/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | 8.6.5.8 - Possible single bottom jack. Installation year says 2002, but it appears this unit was an older unit that was modernized around 2002. Provide documentation to prove unit does not have a single bottom jack. | 1/31/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Check the hoistway door closers for proper closing. | 1/31/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | All smoke and heat detectors shall be landed into the controller and checked from proper operation and function. | 1/31/2025 |
| MO Minimum : Elevators | (K) - Car Platforms and Car Slings | (K)4 | Yes | No | There is no data tag on the controller or crosshead. | 1/31/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | There is no phone line. | 1/31/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Yes | No | Permanent code compliant lighting shall be provided in the machine room. | 1/31/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Guard or gutter pipes conveying water over the pump unit. | 1/31/2025 |
| A17.1-1996 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 211.9 | Yes | No | Hoistway doors shall be numbered. | 1/31/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Yes | No | An MCP is required on-site. | 1/31/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Yes | No | The pit light shall be operational and shall be guarded. | 1/31/2025 |