Inspection
Inspection Details
Equipment ID
7528
7528
Inspection Date
2/14/2025
2/14/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
480
480
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
25
25
External ID
4aac1cae-3738-40f8-9523-6842691bb3c3
4aac1cae-3738-40f8-9523-6842691bb3c3
Location
Warren County Justice Center
104 W BOONESLICK RD, WARRENTON, MO
Phone: (636) 456-3331
104 W BOONESLICK RD, WARRENTON, MO
Phone: (636) 456-3331
Owner
Attn: Warren County Justice Center
Warren County Justice Center
104 W Booneslick Rd, Ste B, Warrenton, MO 63383
Phone: (000) 000-0000
Email: dstotler@warrencountymo.org
Warren County Justice Center
104 W Booneslick Rd, Ste B, Warrenton, MO 63383
Phone: (000) 000-0000
Email: dstotler@warrencountymo.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 5/20/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | The muffler leaks oil, repair. | 5/20/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/20/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Yes | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a non-combustible frame with a clear protective vision plate over it | 1/5/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.19.15 Emergency Communications | Yes | No | A visual indication on the same panel as the "PHONE" push button shall be provided to acknowledge that two-way communications link has been established. | 1/5/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.10.2.2.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The two-way communication means within the car shall include a means to verify operablility of the line meeting the requirements of 2.27.1.1.6. If means other than a telephone line are used for two-way communications, similar verification of this equivlent means shall be performed. | 1/5/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.7.2.15.2 | Yes | No | The illuminated signal for emergency power shall operate as required. | 1/5/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.7.2.16.4 | Yes | No | The car shall run correctly on emergency power. The car ran up to verify the ability to light the load, but would not respond after first run. | 1/5/2025 |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.13.1(l)(Door Restrictor) | Yes | No | The car door shall be restricted from opening when in the closed position anywhere outside the unlocking zone. | 1/5/2025 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 8.6.4.8 Machine Room and Machinery Space | Yes | No | Pieces of the drop ceiling are missing in the machine room and shall be installed/replaced. | 1/5/2025 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3 | Yes | Yes | The new elevator controller is to be connected to the building security system. Once this is complete, a re-inspection shall be performed to verify it will be rendered inoperative when on fire service operation. | 1/5/2025 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | Yes | No | The correct schematics shall be in the machine room | 1/5/2025 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.10.2.2.5(a) | Yes | No | The lighting in the pit shall provide an illumination of no less than 11 1X(10ft) at the pit floor. | 1/5/2025 |
| A17.1-2016 : Elevators | 3.17 - Door and gate equipment | 2.13 | Yes | No | The door operator kinetic energy tag shall be filled out to indicate the minimum door closing times. | 1/5/2025 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | Yes | No | A duplex GFCI receptacle shall be provided in the machine room. | 1/5/2025 |
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.9 | Yes | No | A data plate shall be provided indicating the code in effect at the time of the alteration and the applicable requirements of section 8.7. | 1/5/2025 |