Inspection
Inspection Details
Equipment ID
7858
7858
Inspection Date
2/10/2025
2/10/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dequarius Millett
Dequarius Millett
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
550
550
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
N/A
N/A
External ID
7dd87a44-8cbe-40f8-bd01-a3530585aa67
7dd87a44-8cbe-40f8-bd01-a3530585aa67
Location
Sigma Chemical-Cherokee Bldg
165 Cherokee St, St. Louis, MO
Phone: (314) 713-4729
165 Cherokee St, St. Louis, MO
Phone: (314) 713-4729
Owner
Attn: John Klipsch
Sigma Chemical
PO Box 14508, St. Louis, MO 63178
Phone: (314) 771-5765 Ext: 3968
Email: john.klipsch@milliporesigma.com
Sigma Chemical
PO Box 14508, St. Louis, MO 63178
Phone: (314) 771-5765 Ext: 3968
Email: john.klipsch@milliporesigma.com
Billing
Attn: John Klipsch
Sigma Chemical
3300 S 2nd St, St. Louis, MO 63118
Phone: (314) 771-5765 Ext: 3968
Email: john.klipsch@milliporesigma.com
Sigma Chemical
3300 S 2nd St, St. Louis, MO 63118
Phone: (314) 771-5765 Ext: 3968
Email: john.klipsch@milliporesigma.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Clean pit. | 4/22/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A copy of the MCP shall be kept in the machine room for each elevator | 6/2/2023 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)6 | No | No | Replace missing capacity, No Passengers, class loading and elevator ID signage in car | 6/2/2023 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)6 | No | No | Post missing capacity sign. | 6/1/2023 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)6 | No | No | Post no passengers sign. | 6/1/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Controller cooling fan not working, replace. | 6/1/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Provide guard on bulbs in the elevator machine room. | 6/1/2023 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Remove screws that are penetrating on all hoistway walls. | 6/1/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Provide machine room door to be self closing. | 6/1/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 6/1/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | No | No | Provide audible indicator to work on Phase I recall. | 6/1/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Need to replace missing Class loading signage in car | 9/24/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | Yes | No | Need to repair non-working fire service Phase I audible signal in car. Re-inspection required | 9/3/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Door closing audible alarm is not working. Re-inspection required | 9/3/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | Yes | No | Auxiliary lighting inoperable, repair or place. | 4/25/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell inoperable, and shall be repaired or replaced. | 4/25/2025 |