Inspection
Inspection Details
Equipment ID
7851
7851
Inspection Date
2/12/2025
2/12/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dequarius Millett
Dequarius Millett
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
450
450
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
N/A
N/A
External ID
04ab6596-896a-416f-aaeb-acf1000878b0
04ab6596-896a-416f-aaeb-acf1000878b0
Location
Sigma Chemical-Dekalb Bldg
3500 Dekalb St, St. Louis, MO
Phone: (314) 713-4729
Email: chuck.montgomery@milliporesigma.com
3500 Dekalb St, St. Louis, MO
Phone: (314) 713-4729
Email: chuck.montgomery@milliporesigma.com
Owner
Attn: John Klipsch
Sigma Chemical
PO Box 14508, St. Louis, MO 63178
Phone: (314) 771-5765 Ext: 3968
Email: john.klipsch@milliporesigma.com
Sigma Chemical
PO Box 14508, St. Louis, MO 63178
Phone: (314) 771-5765 Ext: 3968
Email: john.klipsch@milliporesigma.com
Billing
Attn: John Klipsch
Sigma Chemical
3300 S 2nd St, St. Louis, MO 63118
Phone: (314) 771-5765 Ext: 3968
Email: john.klipsch@milliporesigma.com
Sigma Chemical
3300 S 2nd St, St. Louis, MO 63118
Phone: (314) 771-5765 Ext: 3968
Email: john.klipsch@milliporesigma.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Replace seal between head and cylinder flanges. Seal leaks during pressure relief test | 4/24/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Cab fire service light on when car not on recall. Conversly, light extingushes when car is on recall need reapair | 4/24/2019 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)1 | No | No | Replace seal between head cylinder flanges. Seal leaks during pressure relief test. | 7/5/2023 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Cab fire service light inoperative on recall. Repair | 12/5/2019 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate. | 7/5/2023 |
| MO Minimum : Elevators | (A) - Hoistways | (A)5 | No | No | Left side lower panel door guide shoe is broken. Repair | 7/5/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell and light are inoperative. Repair. | 12/5/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Cab fire service inoperative on recall, repair. Reinspect by 1/5/2020 | 2/27/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Cab fireman's jewel visual signal inoperative. Repair within 30 days. | 6/9/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | 8.6.5.16.5 OSV NOT SEALED TEST DUE IN 2021 | 7/5/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A copy of the MCP shall be kept in the machine room for each elevator | 5/22/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current copy of the state operating certificate shall be displayed in the elevator machine room | 5/22/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency alarm in car shall be made operable. Re-inspection required | 5/20/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | OSV is not sealed. Noted in last inspection. Perform required testing, seal & tag within 90 days. Re-inspection required | 5/20/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A copy of the MCP shall be kept in the machine room for each elevator | 7/5/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 7/5/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency alarm in car is not working, may need battery replaced. Re-inspection required | 9/28/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Provide MCP. | 7/5/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit. | 5/24/2023 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)1 | No | No | Remove mounted fire extinguisher from inside the elevator. See ‘96 204.3a | 5/24/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 (Re-Inspection) | Yes | No | The sprinkler head in the elevator machine space is required to have a heat detector to activate the shunt trip disconnect before the application of water. Heat detectors shall be installed within 2’ of each sprinkler head to activate the shunt trip disconnect. | 10/9/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.1 Not less than two lamps | No | No | At least two light fixtures are required for proper illumination inside the elevator cab, only one light fixture was in operation on the day of inspection. Repair fixture. | 10/24/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Firefighters Phase 2 operation shall be tested. | 2/25/2025 |