Inspection
Inspection Details
Equipment ID
25887
Inspection Date
1/20/2025
Inspection Type
Annual Inspection
Inspector Name
Thomas McGrath
Mechanic Name
Christian Schickedanz
Relief Valve Pressure
N/A
Slide
none recorded
Governor Rope Pull
none recorded
Door Closing Force
none recorded
External ID
61e8bbe6-ef11-4e81-b858-dc6660a162eb
Location
Residence Inn by Marriott
8125 Forsyth, Clayton, MO
Phone: (314) 630-9312
Email: tflacke@midas.build
Owner
Attn: Kathy Prainito
Midas Clayton, LLC
1804 Borman Circle Dr, Ste 100, St. Louis, MO 63146
Phone: (314) 764-4262
Email: KPrainito@MidasHospitality.com
Violations
|
Code
|
Item
|
Section
|
Reinspection
|
Red Tag
|
Reason For Violation
|
Fixed Date
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
The in car emergency telephone shall be operational.
|
1/26/2023
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
Yes
|
No
|
Patch all holes and penetrations in the hoistway.
|
1/26/2023
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.10.2.2.1(q)
|
Yes
|
No
|
An emergency generator is being installed. Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator.
|
1/26/2023
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
Yes
|
Yes
|
All fire alarm initiating devices and phases of fire service shall be tested.
|
1/26/2023
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
2.27.2.3 (Elevator Emergency Power Illuminated Signal)
|
No
|
No
|
Elevator tested on standby emergency generator power it passed, but the emergency power bezel in the lobby went out while the elevators werwe running on emergency power. Light has to remain on until normal power is restored. Reinspection maximum 30 days
|
6/26/2024
|
|
A17.1-2016 : Elevators
|
2.13 - Governor, Overspeed Switch, and Seal
|
8.6.4.19.3
|
Yes
|
No
|
Make repairs to elevator so testing can be completed.
|
3/11/2025
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
Yes
|
No
|
Emergency power must be tested.
|
3/11/2025
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
Post certificate in machine room.
|
3/19/2025
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(a)(1)
|
No
|
No
|
Maintenance record have no entries.
|
3/19/2025
|
|
A17.1-2016 : Elevators
|
1.19 - Car Ride
|
2.15.2
|
No
|
No
|
Car guides need replaced
|
3/24/2026
|