Inspection
Inspection Details
Equipment ID
19567
19567
Inspection Date
2/21/2025
2/21/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Dequarius Millett
Dequarius Millett
Mechanic Name
Paul Stuhlsatz
Paul Stuhlsatz
Relief Valve Pressure
N/A
N/A
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
N/A
N/A
External ID
e3ab4a63-5342-406a-a6ac-02fa64e546a4
e3ab4a63-5342-406a-a6ac-02fa64e546a4
Location
Air Products Prism Membranes
11444 Lackland Rd, St. Louis, MO
Phone: (314) 392-3600
11444 Lackland Rd, St. Louis, MO
Phone: (314) 392-3600
Owner
Attn: Jim Riley
Air Products Prism Membranes
11444 Lackland Rd, St. Louis, MO 63146
Phone: (314) 392-3600
Email: rileyjb@airproducts.com
Air Products Prism Membranes
11444 Lackland Rd, St. Louis, MO 63146
Phone: (314) 392-3600
Email: rileyjb@airproducts.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Clean oil from elevator pit. | 7/23/2018 |
| conversion | conversion | n/a | No | No | Repair cab emergency lights | 7/23/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.16 - Rated load, platform area, and data plate | 8.11.2.1.1(p) | No | No | There car capacity plate inside the elevator stating the rated load of the car is unreadable and shall be replaced. | 10/7/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | No | No | The elevator machine room door shall be repaired to be self-closing and self-locking and shall be operable from the interior space without the use of a key. | 10/7/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The fireman's emergency service instructions are unreadable inside the car and shall be replaced. | 10/7/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | The rear car door direction arrow has been damaged and shall be replaced to operate as required | 10/7/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The current state operating certificate needs to be posted in the machine room in a non-combustible frame. | 10/7/2025 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | OSV is not sealed and needs full load test and tripping speed checked. Re-inspection required | 12/20/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Need to replace direction arrow in cab, front & back | 10/7/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2 way communication is not working when the power is off. Re-inspection required | 10/23/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | Yes | No | Auxiliary lighting inoperable, repair or replace. | 2/21/2025 |