Inspection
Inspection Details
Equipment ID
23205
23205
Inspection Date
2/24/2025
2/24/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Mitchell McNeely
Mitchell McNeely
Mechanic Name
Thomas Suedkamp
Thomas Suedkamp
Relief Valve Pressure
Na
Na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
20
20
External ID
99ac26aa-fa59-4689-a5ea-1e5502d94eb0
99ac26aa-fa59-4689-a5ea-1e5502d94eb0
Location
Alinea Town & Country
12831 Daylight Dr, St. Louis, MO
Phone: (314) 965-6565
12831 Daylight Dr, St. Louis, MO
Phone: (314) 965-6565
Owner
Attn: Stacey Derrington
Alinea Town & Country
12831 Daylight Dr, St. Louis, MO 63131
Phone: (314) 965-6565
Email: almanager@thealinea.com
Alinea Town & Country
12831 Daylight Dr, St. Louis, MO 63131
Phone: (314) 965-6565
Email: almanager@thealinea.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.1.4(l) | Yes | Yes | No monthly fire service test logs. | 10/24/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide detailed MCP and post on controller. Remove documents from car top. | 12/21/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Clean pit. | 12/21/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 12/21/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide detailed MCP. 2ND NOTICE | 12/21/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Clean pit. | 12/21/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | Clean car top. | 12/21/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A copy of the MCP shall be kept in the elevator machine room for each elevator | 4/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 2.11 | No | No | Re-install missing hoistway door retainers | 4/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Failed Cat 1 standby power test. Battery lowering system in not getting the elevator to the floor to let occupants out. Re-inspection required | 4/23/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 2.11 | No | No | Re-install missing hoistway door retainers | 4/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.2.7 | Yes | No | Failed Cat 1 standby power test. Battery lowering system in not getting the elevator to the floor to let occupants out. Re-inspection required | 4/23/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 2.11 | No | No | Re-install missing hoistway door retainers | 4/24/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Failed Cat 1 standby power test. Battery lowering system is not getting the elevator to the floor to let occupants out. Re-inspection required | 2/24/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 2.11 | No | No | Need to re-install missing hoistway door retainers | 6/24/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency two way communication is inoperable. Re-inspection is required |