Inspection
Inspection Details
Equipment ID
13124
13124
Inspection Date
2/6/2025
2/6/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Benjamin Postawko
Benjamin Postawko
Relief Valve Pressure
340
340
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
25
25
External ID
fa8fd693-da5a-4d6a-935b-e133966fc7f2
fa8fd693-da5a-4d6a-935b-e133966fc7f2
Location
Riverview Garden Apartments
8612 Halls Ferry Rd, St. Louis, MO
Phone: (314) 647-4422
8612 Halls Ferry Rd, St. Louis, MO
Phone: (314) 647-4422
Owner
Attn: Intrepid Realty
Intrepid Realty
8612 Halls Ferry Rd, St. Louis, MO 63147
Phone: (000) 000-0000
Email: j.vanwinkle@propertyresouce.net
Intrepid Realty
8612 Halls Ferry Rd, St. Louis, MO 63147
Phone: (000) 000-0000
Email: j.vanwinkle@propertyresouce.net
Billing
Attn: Intrepid Realty
Intrepid Realty
8612 Halls Ferry Rd, St. Louis, MO 63147
Phone: (000) 000-0000
Email: corporate@propertyresource.net
Intrepid Realty
8612 Halls Ferry Rd, St. Louis, MO 63147
Phone: (000) 000-0000
Email: corporate@propertyresource.net
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Car emergency lighting does not work. | 8/17/2026 |
| conversion | conversion | conversion - reinspect | Yes | No | Car door restrictor shall work. | 5/22/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room door shall be self-closing and self-locking. | 8/17/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Provide a current tested fire extinguisher in the elevator machine room. | 8/17/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Replace the missing braille/tactile plates on the 2nd and 3rd floor. | 8/17/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Photo eye detectors on mechanical car door are not working and shall be repaired or replaced as needed. | 2/14/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Provide a working door restrictor. | 2/14/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | In car emergency light shall work. | 8/17/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency bell shall work. | 2/14/2024 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Phase 2 halo ring is worn and unreadable, replace as needed. | 2/14/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | Overspeed Valve test still needs to be conducted. | 2/6/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The required pressure/weight testing shall still be conducted. | 2/6/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | Yes | No | Controller workspace is obstructed by door such that the controller door cannot be fully opened. | 2/6/2025 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | Yes | No | Machine room door shall be self-closing and self-locking. Lock shall not be defeated. | 2/6/2025 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.1.1 | Yes | No | Machine room door shall have proper fire rating and labeled as such. | 2/6/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Fire alarm initiating devices (FAID) shall be connected and tested. | 2/6/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. There is no dial tone. | 2/6/2025 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7 | Yes | No | Car lighting - all lamps shall work. No 110v power connected. | 2/6/2025 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7 | Yes | No | Lamps (overhead cab lighting) shall be guarded. | 2/6/2025 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 | Yes | No | Machine room disconnecting means shall be provided with a compliant mechanical auxiliary contact to disconnect the load from the auxiliary power supply. | 2/6/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 3.26.10 | Yes | No | Battery lowering shall work and be tested. | 2/6/2025 |
| A17.1-2016 : Elevators | 1.2 - Stop Switches | 2.26.2.5 | Yes | No | Stop switch shall work. It is water damaged. | 2/6/2025 |
| A17.1-2016 : Elevators | 3.2 - Car top light and outlet | 2.14.7.1.4 | Yes | No | Cartop light does not work. No 110v. | 2/6/2025 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Hoistways shall be of solid construction. Repair multiple fire penetrations. | 2/6/2025 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Hoistways shall be of solid construction and fire rated. Remove wood materials from walls and setbacks. | 2/6/2025 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 | Yes | No | 2.2.5.1 - Pit lighting shall not be less than 10fc at the pit floor. | 2/6/2025 |
| A17.1-2016 : Elevators | 1.4 - Sills and car floor | 2.11.10.2 | Yes | No | Lobby lighting at first floor is less than 5fc. | 2/6/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Hydraulic fluid contaminated with large quantity of water. | 2/6/2025 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 8.6.4.8 Machine Room and Machinery Space | Yes | No | Machine room - remove combustible wood material from walls. | 2/6/2025 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 | Yes | No | Machine room - oil line shut off valve access obstructed by main line disconnect. | 2/6/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | Yes | No | Location of 110v and mainline feeders shall be labeled in machine room (not sharpie). | 2/6/2025 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7 | Yes | No | Lamps (overhead cab lighting) shall be guarded. | 3/6/2025 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | Yes | No | Machine room door shall be self-closing and self-locking. Lock shall not be defeated. | 3/6/2025 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.1.1 | Yes | No | Machine room door shall have proper fire rating and labeled as such. | 3/6/2025 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | Yes | No | Machine room lighting shall be at least 19fc at base of controller. | 3/6/2025 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.8.1 | Yes | No | In the machine room remove combustible wood material from walls of cover properly with fire rated approved materials. | 3/6/2025 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.8.1 | Yes | No | Spray foam shall be removed or covered with proper fire preventative. | 3/6/2025 |
| A17.1-2016 : Elevators | 2.6 - Ventilation | 2.7.9.2 | Yes | No | Proper ventilation shall be provided, either natural or mechanical. | 3/6/2025 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Yes | No | A proper ABC rated fire extinguisher shall be provided, with current test tag. | 3/6/2025 |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4.1 | Yes | No | NEC 409.110 - All industrial control panels, including disconnects within them, must be marked with their SCCR to indicate the maximum fault current they can safely withstand; this applies to any component within the panel that is part of the power circuit. | 3/6/2025 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Hoistway has spray foam throughout, spray foam shall be removed or covered with proper fire preventative. | 3/6/2025 |
| A17.1-2016 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 2.1.6 | Yes | No | Hoistway projections shall be covered, with covering at 75 degrees. | 3/6/2025 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.4 | Yes | No | Pit ladder is obstructed by conduit. Relocate conduit to acceptable location. | 3/6/2025 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 | Yes | No | Pit lighting shall be at least 10fc. | 3/6/2025 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | Yes | No | Pit electrical piping, boxes, conduit, etc shall be of weather-resistant construction (wiring for pit light and light are not weather/water resistant). | 3/6/2025 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | Yes | No | Pit service outlet is not GFCI. Replace with proper outlet in weather resistant box with cover. | 3/6/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | All elevator FAID shall be tested. | 3/6/2025 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7 | Yes | No | Lamps (overhead cab lighting) shall be guarded. | 3/21/2025 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.1.1 | Yes | No | Machine room door shall have proper fire rating and labeled as such. | 3/21/2025 |
| A17.1-2016 : Elevators | 2.6 - Ventilation | 2.7.9.2 | Yes | No | Proper ventilation shall be provided, either natural or mechanical. Added 3/6/25 - In wall vent (added 2025) does not have fire damper/not fire resistant. Openings in machine rooms and space enclosures shall be protected with access doors having a fire protection rating conforming with the requirements of the building code. Wall vent shall be equipped with a spoke shutter in compliance with NFPA 72. | 3/21/2025 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.1.1 | Yes | No | Machine room door shall have proper fire rating and labeled as such. | 3/31/2025 |
| A17.1-2016 : Elevators | 2.6 - Ventilation | 2.7.9.2 | Yes | No | Proper ventilation shall be provided, either natural or mechanical. Added 3/6/25 - In wall vent (added 2025) does not have fire damper/not fire resistant. Openings in machine rooms and space enclosures shall be protected with access doors having a fire protection rating conforming with the requirements of the building code. Wall vent shall be equipped with a smoke shutter in compliance with NFPA 72. | 3/31/2025 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Machine Room shall have proper Fire Extinguisher and shall have current monthly/annual test tag. | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | MCP - Fire Service must be tested and properly documented monthly on Log Sheet | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit floor shall be free of accumulation of water and/or oil. Check packing for excessive leaking. Investigate/repair water leak. Remove rust from pit equipment , repair/replace as needed, apply rust prevention treatment to all pit steel |