Inspection
Inspection Details
Equipment ID
24514
24514
Inspection Date
2/12/2025
2/12/2025
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
24
24
External ID
d1457b2e-1976-470e-a0ff-c4405a9fd632
d1457b2e-1976-470e-a0ff-c4405a9fd632
Location
Aloft Hotels
4245 Duncan Ave, St. Louis, MO
Phone: (000) 000-0000
4245 Duncan Ave, St. Louis, MO
Phone: (000) 000-0000
Owner
Attn: Kathy Prainito
Midas Cortex, LLC
1804 Borman Circle Dr, St. Louis, MO 63146
Phone: (314) 991-1158
Email: KPrainito@midashospitality.com
Midas Cortex, LLC
1804 Borman Circle Dr, St. Louis, MO 63146
Phone: (314) 991-1158
Email: KPrainito@midashospitality.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.11 - Hoistway smoke control | 2.1.4 | x | The powered hoistway vent in the overhead shall automatically open upon detection of smoke in the elevator lobbies or hoistway, and upon power failure. | 5/18/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | x | The powered hoistway vent in the overhead shall be sealed with masonry or other approved solid material. | 5/18/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.27 - Crosshead data plate | 2.16.3 | x | A crosshead data tag meeting the requirements of A17.1 - 2.16.3 and 2.20.2.1 shall be installed. | 5/18/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 8.11.2.1.4(h) | x | The penetrations in the overhead shall be sealed. | 5/18/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | x | Emergency power operation of the elevator shall be tested. | 4/5/2021 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. | 4/5/2021 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone is still not operational. | 6/23/2021 | |
| MO Minimum : Elevators | (A) - Hoistways | (A)1 | Install missing fire stopsopn hoistway doors | 9/21/2022 | ||
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(b)(1) | Remove prints and maintenance records etc from the top of the car | 9/21/2022 | ||
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Perform monthly fire service and document on log in machine room | 9/21/2022 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | Remove storage from the top of the car(maintenance control plan) | 6/26/2023 | ||
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Perform monthly fire service and document on log in machine room | 6/26/2023 | ||
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 2.11 | x | Replace missing fire stop on 5th floor hoistway dooe | 6/26/2023 | |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Perform monthly fire service testing and document on log in machine room | 3/18/2024 |