Inspection
Inspection Details
Equipment ID
17857
17857
Inspection Date
2/26/2025
2/26/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Vernon Livergood
Vernon Livergood
Mechanic Name
Jeremiah Brockway
Jeremiah Brockway
Relief Valve Pressure
Slide
00
00
Governor Rope Pull
00
00
Door Closing Force
20
20
External ID
9cefcb94-b64e-43e7-bfad-19ce485a4552
9cefcb94-b64e-43e7-bfad-19ce485a4552
Location
Independence Regional Health Center
19600 E 39th St S, Independence, MO
Phone: (816) 698-7000
Email: randall.murphy@hcamidwest.com
19600 E 39th St S, Independence, MO
Phone: (816) 698-7000
Email: randall.murphy@hcamidwest.com
Owner
Attn: Randall Murphy
Center Point Medical Center
19600 E 39th St S, Independence, MO 64057
Phone: (816) 698-7093
Email: randall.murphy@hcamidwest.com
Center Point Medical Center
19600 E 39th St S, Independence, MO 64057
Phone: (816) 698-7093
Email: randall.murphy@hcamidwest.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | no records on site | 7/10/2025 |
| A17.1-2016 : Elevators | 2.17 - Drive machine brake | 8.7.2.25 | No | No | new mach. no rope gripper | 2/25/2021 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | No | No | couldnt test emg power at time of insp | 2/25/2021 |
| A17.1-2016 : Elevators | 2.16 - Overhead Beam and Fastenings | 8.7.2.9 | No | No | no report from lic. prof. eng. on support for new floor an mach. beams | 7/10/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | No | No | standby power test didnt work properly | 2/25/2021 |
| A17.1-2016 : Elevators | 2.17 - Drive machine brake | 8.7.2.25.1 | No | No | no rope gripper or emg. brake | 2/25/2021 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | no mcp on site | 7/10/2025 |
| A17.1-2016 : Elevators | 2.16 - Overhead Beam and Fastenings | 8.7.2.9 | No | No | no report on mach.room floor over hoistway by prof. eng. | 6/24/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt. on display | 6/24/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | couldnt test at this time scheduled for april | 2/27/2023 |
| A17.1-2016 : Elevators | 2.16 - Overhead Beam and Fastenings | 8.7.2.9 | No | No | no report on mach. room floor by prof. eng. | 7/10/2025 |
| A17.1-2016 : Elevators | 2.17 - Drive machine brake | 8.7.2.25.1 | Yes | No | emg. brake was not installed as per code | 2/27/2023 |
| A17.1-2016 : Elevators | 2.17 - Drive machine brake | 8.6.4.19.11 Ascending Overspeed Protection, Unintended Movement Devices, and Emg Brake | Yes | No | unintended motion failed | 2/27/2023 |
| A17.1-2016 : Elevators | 4.1 - Car platform guard | 2.15.9 | No | No | platform guard needs to be 48ins. with emg. brake | 6/12/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt. displayed | 6/24/2024 |