Inspection
Inspection Details
Equipment ID
12586
12586
Inspection Date
3/5/2025
3/5/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Nathaniel Smith
Nathaniel Smith
Relief Valve Pressure
580
580
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
9ba4a682-6a3f-4d7f-a045-b93a25416242
9ba4a682-6a3f-4d7f-a045-b93a25416242
Location
Dicks Sporting Goods
200 W County Ctr, Des Peres, MO
Phone: (314) 288-2020
200 W County Ctr, Des Peres, MO
Phone: (314) 288-2020
Owner
Attn: Westfield- Dicks
Westfield- Dicks
44 W County Ctr, Des Peres, MO 63131
Phone: (000) 000-0000
Westfield- Dicks
44 W County Ctr, Des Peres, MO 63131
Phone: (000) 000-0000
Billing
Attn: ATIS – Certificate Mgmt
Dick’s Sporting Goods
2127 Innberbelt Business Center Dr, Ste 210, St. Louis, MO 63114
Phone: (314) 441-3983
Email: dsg@atis.com
Dick’s Sporting Goods
2127 Innberbelt Business Center Dr, Ste 210, St. Louis, MO 63114
Phone: (314) 441-3983
Email: dsg@atis.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.7 - Car door or gate | 112.2a | No | No | Elevator will run with car gate open 3 1/2". Maximum opening is 2". Reinspect within 30 days. | 11/5/2020 |
| A17.1-1996 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 1206.2(c) | No | No | Clean elevator car top. | 11/5/2020 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV installed and not sealed. Perform OSV test on or before next annual inspection. | 4/28/2021 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Expired | 9/1/2022 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Provide working pit light. | 9/1/2022 |
| A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(4) | No | No | Packing (left jack) worn and leaking. | 9/1/2022 |
| A17.1-1996 : Elevators | 1.8 - Door closing force | 1001.2(a)(8) | Yes | No | Door force exceeds 30#. | 9/1/2022 |
| A17.1-1996 : Elevators | 1.16 - Rated load, platform area, and data plate | 207 | No | No | There is no car capacity plate inside the elevator stating the rated load of the car, as required. | 11/12/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator alarm bell inside the elevator is not working. Check and repair the alarm bell for proper operation and passenger safety. Reinspection required. | 11/12/2024 |
| A17.1-1996 : Elevators | 3.19 - Guide rails fastening and equipment | 1001.2(c)(25) | No | No | 200.7b(1)(c) The guide rail fishplate is missing a bolt the right side looking in the hoistway between the 1st and 2nd landing. | 11/12/2024 |
| A17.1-1996 : Elevators | 1.4 - Sills and car floor | 1001.2(a)(4) | No | No | 204.2b Flooring has been added that interferes with the opening of the car operating panel denying access to the emergency battery for the alarm bell and emergency lighting. Readjust flooring or car operating panel. | 11/12/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher in the machine room shall be serviced, the last annual service tag indicates it was serviced in 2022. | 11/12/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator alarm bell inside the elevator is not working. Check and repair the alarm bell for proper operation and passenger safety. Re-inspection required | 12/10/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Bell not working. | 3/5/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Provide current year tested fire extinguisher in the elevator machine room. | 11/12/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Provide existing alarm bell to work. | 7/2/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Clean the pit. | 11/12/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair inoperative emergency Alarm | 1/16/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean the elevator pit | 11/12/2024 |