Inspection
Inspection Details
Equipment ID
26757
26757
Inspection Date
2/10/2025
2/10/2025
Inspection Type
New Installation
New Installation
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Benjamin Postawko
Benjamin Postawko
Relief Valve Pressure
NA
NA
Slide
9.25"
9.25"
Governor Rope Pull
50/112
50/112
Door Closing Force
24
24
External ID
d2c124b7-d80d-4ce5-8775-df88643bbd05
d2c124b7-d80d-4ce5-8775-df88643bbd05
Location
Broadway Lodging Tower #2
1104 E Walnut, Columbia, MO
Phone: (314) 313-7077
Email: msevers@paric.com
1104 E Walnut, Columbia, MO
Phone: (314) 313-7077
Email: msevers@paric.com
Owner
Attn: Broadway Lodging, LLC
Broadway Lodging, LLC
#5 McBride & Sons Center, Chesterfield, MO 63005
Phone: (000) 000-0000
Email: msevers@paric.com
Broadway Lodging, LLC
#5 McBride & Sons Center, Chesterfield, MO 63005
Phone: (000) 000-0000
Email: msevers@paric.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Two-way communication in car shall work. | 2/28/2025 | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Rescue communications system (7th floor) to be tested. | 2/28/2025 | |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | x | Machine space lighting at 8th landing shall be at least 19fc. | 2/28/2025 | |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | x | Fill fire/smoke penetrations with appropriate fire rated caulking. | 2/28/2025 | |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | x | Top of hoistway - wire-way cut/damaged. Repair/replace. | 2/28/2025 | |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | x | Top of hoistway - Multiple knockout plugs missing. | 2/28/2025 | |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | x | Top of hoistway - GFI not working. | 2/28/2025 | |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | x | Hoistway - 4x4 electrical box missing cover. | 2/28/2025 | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.6 Sump Pump Covers | x | Sump cover is too small and does not completely cover sump hole. | 2/28/2025 | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.4 | x | Sump outlet shall be a dedicated simplex outlet. | 2/28/2025 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | x | "In case of fire" signage missing. Permanently install at all floors. | 2/28/2025 | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | x | x | Pit heat detector shall not be less than 48" from pit floor or remove. | 2/28/2025 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | x | x | Smoke/heat detectors shall be at least 3 feet from HVAC register. | 2/28/2025 |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 2.11 | x | 2.11.6.3 - Landing smoke doors shall work and be tested with FAID. | 2/28/2025 | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | x | x | All elevator FAID to be tested. | 2/28/2025 |