Inspection
Inspection Details
Equipment ID
6056
6056
Inspection Date
3/6/2025
3/6/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Mitchell McNeely
Mitchell McNeely
Mechanic Name
Bradley Tramel
Bradley Tramel
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
23
23
External ID
558ee7b2-e31d-4932-a884-756a9afd90b4
558ee7b2-e31d-4932-a884-756a9afd90b4
Location
The 900 Walnut Building
900 Walnut St, St. Louis, MO
Phone: (314) 335-3800
900 Walnut St, St. Louis, MO
Phone: (314) 335-3800
Owner
Attn: Angela M. O’Hanlon
900 Walnut Owner LLC and 210 N Tucker Owner, LLC
P210 N Tucker Blvd, Ste 1030, St. Louis, MO 63101
Phone: (314) 335-3802
Alt Phone: (314) 919-7145
Email: hyorg@netrality.com
900 Walnut Owner LLC and 210 N Tucker Owner, LLC
P210 N Tucker Blvd, Ste 1030, St. Louis, MO 63101
Phone: (314) 335-3802
Alt Phone: (314) 919-7145
Email: hyorg@netrality.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | 1.6 - The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. | 5/20/2019 |
| A17.1-2016 : Elevators | 4.1 - Car platform guard | 2.15.9 | Yes | No | Obstruction in pit will not accommodate a 48" platform guard. Customer will need to request a variance. | 5/31/2023 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.1 Phase I Emergency Recall Operation | Yes | Yes | Test fire service switch at lobby hall station after new one is installed. | 5/31/2023 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | Yes | No | Provide a self-closing and self-locking machine room door. | 5/31/2023 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.1 | Yes | No | Provide a permanent step at the machine room entrance. | 5/31/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Test standby power when installation is complete. | 5/31/2023 |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | Yes | No | Install hoistway duct covers. | 5/31/2023 |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | Yes | No | Remove temporary wiring from hoistway. | 5/31/2023 |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 2.11 | Yes | No | Cover old escutcheon holes in hoistway doors. | 5/31/2023 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | Yes | No | Install machine room duct covers. | 5/31/2023 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | Yes | No | Remove all temporary wiring from the machine room. | 5/31/2023 |
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.9 | Yes | No | 8.10.1.1.4 - Provide acceptance test tag permanently attached to controller. | 5/31/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | elevator is on emergency generator power and has not been tested. Generator testing shall occur to complete the annual inspection | 7/29/2025 |