Inspection
Inspection Details
Equipment ID
6889
6889
Inspection Date
2/12/2025
2/12/2025
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Bradley Tramel
Bradley Tramel
Relief Valve Pressure
NA
NA
Slide
7"
7"
Governor Rope Pull
150/NA
150/NA
Door Closing Force
NA
NA
External ID
f84f3551-90f8-482a-8ad8-104a258862b6
f84f3551-90f8-482a-8ad8-104a258862b6
Location
Randolph Building
329 Belt Ave, St. Louis, MO
Phone: (314) 781-4551
329 Belt Ave, St. Louis, MO
Phone: (314) 781-4551
Owner
Attn: The Randolph Condominium Association Darin Buford
Rodemeyer-Christel INC
3630 Grandel Square, St. Louis, MO 63108
Phone: (314) 454-0800
Email: dbuford@rcirealty.com
Rodemeyer-Christel INC
3630 Grandel Square, St. Louis, MO 63108
Phone: (314) 454-0800
Email: dbuford@rcirealty.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Install anti-rotation device on the counterweight shackles. | 9/10/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/10/2020 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)2 | Yes | No | The upper final limit shall be operational. | 7/13/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. | 9/10/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide a code compliant MCP including onsite documents. | 1/31/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be displayed in the elevator machine room. | 1/31/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/15/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key. | 3/15/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher shall be up to date. | 4/24/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/24/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key. | 4/24/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | The in car alarm bell shall be operational on main and on auxiliary power. The alarm bell intermittently fails to operate when the button is pushed. | 4/24/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | A cover is missing on a conduit body in the hoistway at the top floor, it shall be replaced. | 4/24/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | The electrical fitting on gate switch is broken and shall be replaced. | 4/24/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Clean machine room. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean off the top of the car. | |
| MO Minimum : Elevators | (I) - Pits | (I)5 | No | No | Clean out the pit | |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | The wind up safety cable should be bronze instead of regular lay cable. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is still not working. |