Inspection
Inspection Details
Equipment ID
13447
13447
Inspection Date
2/18/2025
2/18/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
Christian Schickedanz
Christian Schickedanz
Relief Valve Pressure
NA
NA
Slide
18"
18"
Governor Rope Pull
TBD
TBD
Door Closing Force
23
23
External ID
5844f8cf-0c49-4e06-a759-dc91f2e34573
5844f8cf-0c49-4e06-a759-dc91f2e34573
Location
St Louis Properties #1
3733 Lindell Blvd, St. Louis, MO
Phone: (314) 561-6400
Email: coronadoplacemgr@greystar.com
3733 Lindell Blvd, St. Louis, MO
Phone: (314) 561-6400
Email: coronadoplacemgr@greystar.com
Owner
Attn: St. Louis Properties
St. Louis Properties
3701 Lindell Blvd, St. Louis, MO 63108
Phone: (314) 931-2732
Email: coronadoplacemgr@greystar.com
St. Louis Properties
3701 Lindell Blvd, St. Louis, MO 63108
Phone: (314) 931-2732
Email: coronadoplacemgr@greystar.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 212 | Yes | No | Suspension ropes have rouge and are undersized. Re-inspection required | 10/16/2024 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Pit needs to be cleaned | 4/3/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. Re-inspection required | 10/16/2024 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Pit light does not work | 4/3/2026 |
| A17.1-1996 : Elevators | 3.20 - Governor rope | 1001.2(c)(26) | Yes | No | Governor rope has grease all over it, should not be greased. Clean grease off rope. Re-inspection required | 10/16/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Ropes have been replaced but got twisted during testing. Take corrective action and re-test. Unit left shut down by maintenance company. | 10/16/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing incomplete. Items to be completed: door closing force, SOS, 100% Safety Set, Slide, 125% weight, Emergency light/bell/phone, runby. | 2/18/2025 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Fire service testing must be documented monthly. | 4/3/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/3/2026 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | Machine room door shall be self-closing and self-locking and operable from the interior space without the use of a key. Door cannot be opened inside machine room. | 4/3/2026 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | Machine room lighting needs to be repaired. One or more bulbs are not working. | 4/3/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing incomplete. Items to still be tested: SOS, 100% safety set, 125% weight, emergency light/bell/phone, runby. | 4/10/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing incomplete. Testing still needed: spin test on governor and switch, 125% brake test, full load safety test, emergency phone, emergency light, and emergency bell. | 4/3/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A code compliant MCP and related on-site documentation shall be provided in the machine room. | 4/3/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/3/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self-closing and self-locking. | 4/3/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Items to be completed: 100% Safety Set, Slide, 125% items. | |
| A17.1-1996 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 107.1b | Yes | No | Counterweight runby shall not be less than 6". Currently 1". | |
| A17.1-1996 : Elevators | 4.2 - Hoistway doors | 110 | Yes | No | Replace missing Fire tab on 14R hoistway door. | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Fire Service Testing must be documented monthly in the MCP located in the machine room. | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current State Operating Permit shall be obtained and displayed in the Equipment Room. | |
| A17.1-1996 : Elevators | 2.4 - Machine space | 100.3d | No | No | Machine room door shall be self-closing and self-locking. Door handle cannot be locked. | |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | Machine room lighting needs to be repaired, 1 or more bulbs not working. | |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | Machine Room Fire Extinguisher shall have current monthly/annual test tag. | |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | No | No | Pit shall be kept clean. Remove excess debris. | |
| A17.1-1996 : Elevators | 3.27 - Crosshead data plate | 212.2 | No | No | Suspension ropes shall have proper data tag(s) | |
| A17.1-1996 : Elevators | 4.2 - Hoistway doors | 110 | No | No | Replace missing/damaged pickup rollers on 4R hoistway door. |