Inspection
Inspection Details
Equipment ID
10190
10190
Inspection Date
2/20/2025
2/20/2025
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
NA
NA
Slide
16 3/16"
16 3/16"
Governor Rope Pull
70/675
70/675
Door Closing Force
21
21
External ID
a291669d-93fd-470b-aa98-98c8feea64a1
a291669d-93fd-470b-aa98-98c8feea64a1
Location
700 Market LLC
700 Market St, St. Louis, MO
Phone: (314) 393-9322
700 Market St, St. Louis, MO
Phone: (314) 393-9322
Owner
Attn: Jenna Beaird
The Koman Group
8025 Bonhome Ave, Ste 200, Clayton, MO 63105
Phone: (314) 640-1469
Alt Phone: (314) 933-5800
Email: jbeaird@keeleyproperties.com
The Koman Group
8025 Bonhome Ave, Ste 200, Clayton, MO 63105
Phone: (314) 640-1469
Alt Phone: (314) 933-5800
Email: jbeaird@keeleyproperties.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 2/2/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communications/phone not working reinspection item 30 day maximum | 3/6/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | building currently changing billing 30 day extension has been granted from date of this report | 4/25/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Restrictor is broken and shall be repaired. | 10/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | ALARM BELL SHALL WORK WITH LOSS OF MAIN 120v POWER | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | EMERGENCY LIGHTING SHALL WORK WITH LOSS OF MAIN 120v POWER | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine Room shall have proper Fire Extinguisher and shall have current monthly/annual test tag. No extinguisher present | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | 2 electrical boxes in machine room need to have wiring inside box and covers installed. | |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | MCP - Fire Service must be tested and properly documented monthly on Log Sheet. Almost all are blank. | |
| MO Minimum : Elevators | (A) - Hoistways | (A)1 | No | No | Hoistway door(s) have missing or loose guides on 1st,2nd, and 5th floors. Repair/replace as needed. |