Inspection
Inspection Details
Equipment ID
12090
12090
Inspection Date
3/12/2025
3/12/2025
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Mitchell McNeely
Mitchell McNeely
Mechanic Name
Thomas Suedkamp
Thomas Suedkamp
Relief Valve Pressure
na
na
Slide
29
29
Governor Rope Pull
95/980
95/980
Door Closing Force
23/25
23/25
External ID
b9970828-1360-4f85-be20-67b08ccc719b
b9970828-1360-4f85-be20-67b08ccc719b
Location
Renaissance Grand Hotel
820 Washington Ave, St. Louis, MO
Phone: (314) 621-9600
820 Washington Ave, St. Louis, MO
Phone: (314) 621-9600
Owner
Attn: Marriott St. Louis Grand
Marriott St. Louis Grand
800 Washington Ave, St. Louis, MO 63101
Phone: (314) 333-2326
Alt Phone: (314) 418-5858
Email: STLMGEngineering@marriott.com
Marriott St. Louis Grand
800 Washington Ave, St. Louis, MO 63101
Phone: (314) 333-2326
Alt Phone: (314) 418-5858
Email: STLMGEngineering@marriott.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Repair emergency lights in car. | 11/5/2025 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Emergency light not working. | 12/11/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Repair pit light. | 11/5/2025 |
| A17.1-1996 : Elevators | 3.22 - Wire rope fastening and hitch plate | 1001.2(c)(28) | No | No | Replace anti-rotation devices on counterweights. | 11/5/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light (still) inoperative. | 3/10/2021 |
| A17.1-1996 : Elevators | 2.17 - Drive machine brake | 1001.2(b)(15) | Yes | Yes | Car lowered, stopped and held 125% capacity, however adjustment needs to be made for brake pick gaps to a consistent .005 as per brake data tag. Reinspection only. | 3/28/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light and alarm bell do not work. | 3/28/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the elevator machine room | 11/5/2025 |
| A17.1-1996 : Elevators | 3.16 - Traveling cables and junction boxes | 1001.2(c)(22) | No | No | Repair or replace travel cable due to damage and/or breakage of cable insulation at basement floor loop | 11/5/2025 |
| A17.1-1996 : Elevators | 3.16 - Traveling cables and junction boxes | 1001.2(c)(22) | No | No | Repair/replace travel cable due to damage and/or breakage of cable insulation. Basement floor loop | 11/5/2025 |
| A17.1-1996 : Elevators | 3.16 - Traveling cables and junction boxes | 1001.2(c)(22) | No | No | Repair/replace travel cable due to damage and/or breakage of cable insulation. Basement floor loop | 3/11/2026 |
| A17.1-1996 : Elevators | 3.16 - Traveling cables and junction boxes | 1001.2(c)(22) | Yes | No | Repair/replace travel cable due to damage and/or breakage of cable insulation. Basement floor loop | 4/22/2026 |
| A17.1-1996 : Elevators | 1.14 - Ventilation | 204.3c | No | No | There shall be permanent means of temperature control inside of the elevator machine room. | 4/28/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.2-211.8 | Yes | Yes | Unit failed to perform firefighters operation and is red tagged at this time. | 4/28/2026 |
| A17.1-1996 : Elevators | 1.14 - Ventilation | 204.3c | No | No | There shall be permanent means of temperature control inside of the elevator machine room. |