Inspection
Inspection Details
Equipment ID
12206
12206
Inspection Date
3/11/2025
3/11/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Mitchell McNeely
Mitchell McNeely
Mechanic Name
Thomas Suedkamp
Thomas Suedkamp
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
6b166fa8-6b0e-4d79-a1e2-f846983e26a1
6b166fa8-6b0e-4d79-a1e2-f846983e26a1
Location
Renaissance Grand Hotel- St. Louis
800 Washington Ave, St. Louis, MO
Phone: (314) 621-9600
800 Washington Ave, St. Louis, MO
Phone: (314) 621-9600
Owner
Attn: Marriott St. Louis Grand
Marriott St. Louis Grand
800 Washington Ave, St. Louis, MO 63101
Phone: (314) 333-2326
Alt Phone: (314) 418-5858
Email: STLMGEngineering@marriott.com
Marriott St. Louis Grand
800 Washington Ave, St. Louis, MO 63101
Phone: (314) 333-2326
Alt Phone: (314) 418-5858
Email: STLMGEngineering@marriott.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a | Yes | No | Clean debris from elevator pit. | 1/16/2020 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 1001.2(b)(6) | No | No | Repair air conditioning in machine room. | 9/30/2025 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Clean rubbish from pit. | 9/30/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Reprogram emergency phone. | 4/7/2022 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | No | No | Refasten loose, bottom terminal floor hoistway door sight guard | 9/30/2025 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | No | No | Clean pit. | 9/30/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two way communication inoperable. Re-inspection required | 12/10/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Inspection incomplete. Must perform all the weight test, counter weight buffer, set safeties, 125% brake test | 12/19/2024 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | Yes | No | Phase 2 call cancel is inoperable and shall be repaired or replaced. | 3/11/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Means of two way communication are inoperable and shall be repaired or replaced. | 3/11/2025 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | No | No | Permanent means of temperature control are inoperable and shall be repaired, or replaced. | 9/30/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Means of two way communication are inoperable and shall be repaired or replaced. 2.27.1 | 9/30/2025 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | No | No | Permanent means of temperature control are inoperable and shall be repaired, or replaced. | 9/30/2025 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | No | No | Refasten loose, bottom terminal floor hoistway door sight guard. | 3/31/2026 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | No | No | Permanent means of temperature control are inoperable and shall be repaired, or replaced. | 3/31/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Two-way communication could not be established. Repair/replace this phone for proper operation and passenger safety. Reinspection required. | 3/31/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | The car door operator was out of service and full inspection on the car door operation could not made. Repair car door operator and a reinspection is required to ensure proper operation. | 3/31/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | Yes | No | Fireman’s service operation could not be completed due to the car door operator being out of service. Repair door operator to fireman’s service. Reinspection is required. | 3/31/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. | 3/31/2026 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | No | No | Permanent means of temperature control are inoperable and shall be repaired, or replaced. | 4/7/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Means of two way communication are inoperable and shall be repaired or replaced. | 4/7/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | Call cancel does not work on phase II fire service, needs repaired. Re-inspection required | |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 Door Systems | No | No | Bottom hoistway door sight guard (non vision panel) is loose, needs repaired | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Means of two way communication are inoperable and shall be repaired or replaced. Re-inspection required |