Inspection
Inspection Details
Equipment ID
26758
26758
Inspection Date
2/28/2025
2/28/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Benjamin Postawko
Benjamin Postawko
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
8b7c1d9f-ae36-4366-bfc0-ab10f34db199
8b7c1d9f-ae36-4366-bfc0-ab10f34db199
Location
Broadway Lodging Tower #2
1104 E Walnut, Columbia, MO
Phone: (314) 313-7077
Email: msevers@paric.com
1104 E Walnut, Columbia, MO
Phone: (314) 313-7077
Email: msevers@paric.com
Owner
Attn: Broadway Lodging, LLC
Broadway Lodging, LLC
#5 McBride & Sons Center, Chesterfield, MO 63005
Phone: (000) 000-0000
Email: msevers@paric.com
Broadway Lodging, LLC
#5 McBride & Sons Center, Chesterfield, MO 63005
Phone: (000) 000-0000
Email: msevers@paric.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Two-way communication in car shall work. | 2/28/2025 | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Rescue communications system (7th floor) to be tested. | 2/28/2025 | |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | x | Machine space lighting at 8th landing shall be at least 19fc. | 2/28/2025 | |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | x | Fill fire/smoke penetrations with appropriate fire rated caulking. | 2/28/2025 | |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | x | Top of hoistway and pit - wire-way cut/damaged. Repair/replace. | 2/28/2025 | |
| A17.1-2016 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 2.10.2.3 Toe Board | x | Rear handrail less than required 4" clearance to rear HW wall. | 2/28/2025 | |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 2.11 | x | 1st floor door sill to floor gap approximately 2". Shall be flush. | 2/28/2025 | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) | x | Pump sump not plugged into outlet, finish installation and test operation. | 2/28/2025 | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.4 | x | Sump outlet shall be a dedicated simplex outlet. | 2/28/2025 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | x | "In case of fire" signage missing. Permanently install at all floors. | 2/28/2025 | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | x | x | Pit heat detector shall not be less than 48" from pit floor or remove. | 2/28/2025 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | x | x | Smoke/heat detectors shall be at least 3 feet from HVAC register. | 2/28/2025 |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 2.11 | x | 2.11.6.3 - Landing smoke doors shall work and be tested with FAID. | 2/28/2025 | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | x | x | All elevator FAID to be tested. | 2/28/2025 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | x | No fire extinguisher in machine space or immediately adjacent. | 2/28/2025 |