Inspection
Inspection Details
Equipment ID
8613
8613
Inspection Date
3/20/2025
3/20/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dennis Smith
Dennis Smith
Mechanic Name
Jason Stout
Jason Stout
Relief Valve Pressure
420
420
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
20
20
External ID
60f0bb7e-78ee-4235-b9fe-b336d3774f00
60f0bb7e-78ee-4235-b9fe-b336d3774f00
Location
Commerce Bank- St. Joseph
3303 ASHLAND AVE, SAINT JOSEPH, MO
Phone: (816) 236-5976
3303 ASHLAND AVE, SAINT JOSEPH, MO
Phone: (816) 236-5976
Owner
Attn: Tracy Cameron
Commerce Bank- St. Joseph
328 Felix St, St. Joseph, MO 64501
Phone: (816) 236-5703
Email: tracy.cameron@commercebank.com
Commerce Bank- St. Joseph
328 Felix St, St. Joseph, MO 64501
Phone: (816) 236-5703
Email: tracy.cameron@commercebank.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | No | No | Keep up to date wiring diagrams in the machine room. The wiring diagrams on site are not the correct ones for the elevator. | 6/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | Test and log firefighter operation monthly | 6/1/2022 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Install smoke sensing devices at elevator lobbies except the main designated landing. The smoke sensing devices, when activated, shall return elevator to the main designated landing. | 6/13/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | Yes | Fire initiating devices have been installed but need to be tested with an inspector present. | 6/16/2022 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Remove newly installed fire initiating device at the main landing. Per A17.1-1978 rule 211.3a2 | 6/16/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove non-elevator related material from machine room. (Gallons of paint-water hose-water sprinkler-snow shovel) | 6/20/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone dials out but does not connect. | 6/22/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | No | No | Keep the correct and up to date wiring diagrams for the elevator in the machine room. | 6/20/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 6/20/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | No | No | No audible signal during fire recall | 6/20/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Water accumulated in the elevator pit from the broken water line from the drinking fountain shall be removed. | 3/12/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | phone didnt work |